3.5.2 Midpoint TEACH
Output OFF
0 mm
(500 mm)
(700 mm)
(600 mm)
1000 mm
SP1
SP2
Midpoint
Output ON
Figure 17. Window and Midpoint Example
The Midpoint TEACH uses both the window size and the
TEACH midpoint to determine the actual measurement
window. For example, a window of 200 mm with a midpoint
of 600 mm places the measurement window from 500 mm to
700 mm.
To use Midpoint TEACH:
1. Set the window size.
2. Set the measurement window using
on page 16.
Window Size
The WndSize option sets the window size that the Midpoint TEACH uses to set the setpoint one and setpoint two
thresholds.
The Midpoint TEACH fails if the window is not taught within the valid measurement range.
LE250 Laser Sensor
LE550 Laser Sensor
Window Size Minimum
1 mm
10 mm
Window Size Maximum
250 mm
800 mm
Range
100 mm to 400 mm
100 mm to 1000 mm
Default Window Size
50 mm
300 mm
Navigate: MENU > Dx_OUT > TchMid > WndSize
Remote Input: Available
1. Access the setup mode.
Method
Action
Result
Push Button
Navigate: MENU > Dx_OUT > TchMid > WndSize .
"WndSize" and the current window
size value display.
Remote Input
a. Double-pulse the remote input to enter
setup mode.
b. Three-pulse the remote input to enter
window size mode.
T
T
T
T
T
T
T
T
a. "REMOTE SETUP" displays.
b. "WndSize" and the current value
display.
2. Set the window size.
Method
Action
Result
Push Button
a. Use Down
and Up
to set the desired window size—the
value changes in increments of 2.
b. Press Enter
to save the new value.
a. "WndSize" and the new value
display.
b. The new value flashes and returns
to "TchMid WndSize".
L-GAGE
®
LE250/550 IO-Link Laser Gauging Sensors
www.bannerengineering.com - Tel: 763.544.3164
15