Action
Result
Navigate: MENU > Dx_OUT > TchSPt
"TchSPt Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value is shown on the second line
of the display and flashes before it is saved
and the sensor returns to "Dx_OUT
TchSPt".
TEACH Not Accepted
"FAIL" and a warning message display, and
the sensor returns to "Dx_OUT TchSPt".
Remote Input Instructions
1. Verify the sensor is in Switch mode.
2. Access the TEACH mode.
Action
Result
Single-pulse the remote input.
T
"RMT TCH" and the current measurement
value display.
3. Present the target.
Action
Result
Present the target.
"RMT TCH" and the target's measurement
value display.
4. TEACH the sensor.
Action
Result
Five-pulse the remote input.
T
T
T
T
T
T
T
T
T
"TchSPt Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value displays on the second line
of the display, flashes, and the sensor
returns to Run mode.
TEACH Not Accepted
"FAIL" flashes, the sensor returns to step
3, and "RMT TCH" displays.
3.5.6 Adjust Switch Point
The AdjSPt option manually adjusts the value of the switch point threshold for the discrete output when the sensor is in
Switch mode. The value is adjustable within the sensor's range. This menu is not available when the sensor is in Window,
Alarm, or Health mode.
Navigate: MENU > Dx_OUT > AdjSPt
Remote Input: Not available
Default: 100 mm for the LE250 and LE550 models
3.5.7 Mode
The Mode option sets the output to the desired mode.
Navigate: MENU > Dx_OUT > Mode
Remote Input: Available
Default: Wnd
mode
The following table describes the sensor modes.
L-GAGE
®
LE250/550 IO-Link Laser Gauging Sensors