Technical data
52
Automation Panel 9xD - Hygienic design User's manual V 1.80
For example, a copper strip must be attached to the ground connection at a central grounding point of the control
cabinet or system in which the device is installed. The wire cross section should be as large as possible (at least
2.5 mm²).
4.1.5.2.3 Ethernet interfaces
The Ethernet controller is routed externally via the system unit.
ETH1, ETH2
Variant
RJ45, female
Controller
Intel I210
Wiring
S/STP (Cat 5e)
Transfer rate
10/100/1000 Mbit/s
1)
Cable length
Max. 100 m (min. Cat 5e)
LED "Speed" (b)
On
Off
Yellow
100 Mbit/s
10 Mbit/s
2)
Green
1000 Mbit/s
-
LED "Link" (a)
On
Active
Green
Link (a connection to an
Ethernet network exists)
Blinking (data be-
ing transferred)
1)
Switching takes place automatically.
2)
The 10 Mbit/s transfer rate / connection is only available if LED "Link" is active at the same time.
Driver support
A special driver is required to operate the Ethernet controller. Drivers for approved operating systems are available
for download in the Downloads section of the B&R website (
Information:
Necessary drivers must be downloaded from the B&R website, not from manufacturer websites.