Technical data
4.1.3.2 Installation diagrams
Information:
When installing the Automation Panel 9x3, spacing for air circulation and additional free space for
operating and servicing the device must be taken into account.
The cutout tolerances are +0 mm / -0.5 mm.
Y
X
Z
Panels
Type
Model number
X
Y
Z min.
Z max.
Number of retaining clips
12.1" single-touch
5AP923.1215-00
304
228
1
6
10 pcs.
15.0" single-touch
5AP923.1505-00
359
277
1
6
10 pcs.
19.0" single-touch
5AP923.1906-00
429
347
1
6
12 pcs.
15.6" multi-touch
5AP933.156B-00
403
247.5
1
6
10 pcs.
18.5" multi-touch
5AP933.185B-00
464
284
1
6
10 pcs.
21.5" multi-touch
5AP933.215C-00
530.5
322
1
6
14 pcs.
24.0" multi-touch
5AP933.240C-00
587.5
353
1
6
14 pcs.
Dimension "Z" describes the thickness of the wall or control cabinet plate.
A hex screwdriver is needed to tighten and remove the screw on the retaining clips. The maximum tightening torque
of the retaining clips is 1 Nm.
Automation Panel 9x3 User's manual 2.01
27