Technical data
4.1.4.2 Relative humidity
The following tables show the minimum and maximum relative humidity (at 30°C, non-condensing) of the individual
components that are relevant for limiting the humidity of the complete system. The smallest or largest value must
always be used for this determination. For more detailed information, see technical data or temperature/humidity
diagrams of the individual components.
Panels
Type
Model number
Operation [%]
Storage [%]
Transport [%]
12.1" single-touch
5AP923.1215-00
5 to 90
5 to 90
5 to 90
15.0" single-touch
5AP923.1505-00
8 to 90
8 to 90
8 to 90
19.0" single-touch
5AP923.1906-00
5 to 90
5 to 90
5 to 90
15.6" multi-touch
5AP933.156B-00
5 to 90
5 to 90
5 to 90
18.5" multi-touch
5AP933.185B-00
5 to 90
5 to 90
5 to 90
21.5" multi-touch
5AP933.215C-00 ≤ C0
10 to 90
10 to 90
10 to 90
21.5" multi-touch
5AP933.215C-00 ≥ D0
5 to 90
5 to 90
5 to 90
24.0" multi-touch
5AP933.240C-00
5 to 90
5 to 90
5 to 90
Link modules
Type
Order number
Operation [%]
Storage [%]
Transport [%]
SDL/DVI receiver
5DLSDL.1001-00
5 to 90
5 to 95
5 to 95
SDL3 receiver
5DLSD3.1001-00
5 to 90
5 to 95
5 to 95
SDL4 receiver
5DLSD4.1001-00
5 to 90
5 to 95
5 to 95
4.1.4.3 Vibration and shock
The following table provides an overview of the maximum vibrations and shock values of the complete system.
Limitations are possible due to individual components.
Vibration
Operation
1)
Storage
1)3)
Transport
1)3)
Continuous
Periodic
Automation Panel 9x3
2 to 9 Hz:
1.75 mm amplitude
9 to 200 Hz: 0.5 g
2 to 9 Hz:
3.5 mm amplitude
9 to 200 Hz: 1 g
2 to 8 Hz: 7.5 mm amplitude
8 to 200 Hz: 2 g
200 to 500 Hz: 4 g
2 to 8 Hz: 7.5 mm amplitude
8 to 200 Hz: 2 g
200 to 500 Hz: 4 g
Shock
Operation
2)
Storage
2)3)
Transport
2)3)
Automation Panel 9x3
15 g, 11 ms
30 g, 6 ms
30 g, 6 ms
1)
Testing is performed per EN 60068-2-6.
2)
Testing is performed per EN 60068-2-27.
3)
The specification refers to a device in its original packaging.
4.1.4.4 Degree of protection
In accordance with EN 60529, the Automation Panel 9x3 has IP65 protection on the front and IP20 protection on
the back under the following conditions:
•
The Automation Panel 9x3 is installed correctly (see
"Automation Panel 9x3 - Installation" on page 73
•
All covers and components are installed on the interfaces and slots.
•
All environmental conditions are observed.
The Automation Panel 9x3 additionally has "Type 4X indoor use only" on the front per UL 50 under the same
conditions.
Automation Panel 9x3 User's manual 2.01