HINGE UNIT ASSEMBLY TO THE RIGHT OR LEFT
The burner hinge can be opened both ways, it is therefore possible to
reverse the opening side of the ventilating body.
As a standard, the burner is supplied with the hinge installed on the
right side.
To enable the maximum opening and so facilitate maintenance opera
-
tions, it is recommended to install the hinge on the side of the burner
opposite to the position where the gas train is installed.
In case it is necessary to install the hinge on the left side, proceed
as follows:
• Unscrew the anchoring screws (11) and open the ventilating
body to the amount needed for the removal of the centring pin
(20).
•
Close the burner again by re-tightening the screws (11) and
remove the two hinges and the pin (10).
• Then, remove the screws and the relevant washers (21) on the
left side of the flange and refit them on the right side in corre
-
spondence with the holes left free after removal of the hinges.
•
Fit the hinge unit on the burner left side.
DANGER / ATTENTION
The two hinges (3) must be positioned initially without fully
tightening the four screws (21). It is necessary to first make
sure that the contact surfaces of the two hinges (3) are in
completely in contact with the corresponding surfaces of the
scroll (22). Prior to this, tighten the two nuts and the relevant
washers (23). Do not tighten the nuts too deeply, as this may
make hinge rotation difficult. Carry out the final tightening of the
screws (21) to complete the operation.
•
Open the ventilating body again to make sure that the hinge unit
rotates correctly and re-fit the centring (10) on the side of the
fan flange opposite to the hinge side in order to facilitate closing
again of the burner.
CAUTION / WARNINGS
Each time the burner has to be opened, first disconnect the
connectors to the gas butterfly servomotor, to the diesel
pressure regulator, to the gas solenoid valves and to the diesel
circuit.
23
21
3
3
22
11
23
21
10
0002937230
13 / 38
0006160334_202305
ENGLISH
Summary of Contents for TBML 900 ME
Page 2: ......
Page 35: ...SCHEMI ELETTRICI TBML 600 ME 800 ME 900 ME BT 335 33 38 0006160334_202305 ITALIANO...
Page 36: ...TBML 600 ME 800 ME 900 ME BT 335 34 38 0006160334_202305 ITALIANO...
Page 37: ...TBML 600 ME 800 ME 900 ME BT 335 35 38 0006160334_202305 ITALIANO...
Page 38: ...TBML 600 ME 800 ME 900 ME BT 335 36 38 0006160334_202305 ITALIANO...
Page 39: ...I1 I2 BA I4 I3 TBML 600 ME 800 ME 900 ME BT 335 37 38 0006160334_202305 ITALIANO...
Page 73: ...WIRING DIAGRAMS TBML 600 ME 800 ME 900 ME BT 335 33 38 0006160334_202305 ENGLISH...
Page 74: ...TBML 600 ME 800 ME 900 ME BT 335 34 38 0006160334_202305 ENGLISH...
Page 75: ...TBML 600 ME 800 ME 900 ME BT 335 35 38 0006160334_202305 ENGLISH...
Page 76: ...TBML 600 ME 800 ME 900 ME BT 335 36 38 0006160334_202305 ENGLISH...
Page 77: ...I1 I2 BA I4 I3 TBML 600 ME 800 ME 900 ME BT 335 37 38 0006160334_202305 ENGLISH...
Page 79: ......