TECHNICAL SPECIFICATIONS
MODEL
TBML 900 ME
Maximum natural gas thermal power
kW
9000
Minimum natural gas thermal power
kW
1000
Natural gas operation
Electronic modulation
Natural gas maximum flow rate
Stm³/h
952
Natural gas minimum flow rate
Stm³/h
106
Natural gas minimum pressure
hPa (mbar)
168
Natural gas maximum pressure
hPa (mbar)
500
Diesel fuel maximum flow rate
kg/h
759
Diesel fuel minimum flow rate
kg/h
169
Maximum diesel fuel thermal power
kW
9000
Minimum diesel fuel thermal power
kW
2000
50hz pump motor
kW
2,2
Diesel viscosity
6 cst/20°C - 1,5°E / 20°C
Diesel operation
Electronic modulation
50hz fan motor
kW
18.5
50hz fan motor rpm
r.p.m.
2950
50 hz ignition transformer
2x5kV - 30mA - 230V
50Hz three-phase electrical data
3L - 400V - 37.8A - 22.71kW
50Hz single-phase electrical data
1N - 230V - 2,27A - 0,522kW
Protection rating
IP54
Control box
BT 335
Flame detection
UV photocell
operating ambient air temperature
°C
-15 ÷ +40
Sound pressure**
dBA
84
Sound power***
dBA
99
Weight with packaging
kg
570
Weight without packaging
kg
394,2
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Diesel fuel: Hi = 11.86 kWh/kg = 42.70 Mj/kg
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
*** Acoustic pressure was obtained characterizing the manufacturer's laboratory with a sample source; this measurement has a class 2 accuracy
(engineering class) with a standard deviation of 1.5 dB(A).
6 / 38
0006160334_202305
ENGLISH
Summary of Contents for TBML 900 ME
Page 2: ......
Page 35: ...SCHEMI ELETTRICI TBML 600 ME 800 ME 900 ME BT 335 33 38 0006160334_202305 ITALIANO...
Page 36: ...TBML 600 ME 800 ME 900 ME BT 335 34 38 0006160334_202305 ITALIANO...
Page 37: ...TBML 600 ME 800 ME 900 ME BT 335 35 38 0006160334_202305 ITALIANO...
Page 38: ...TBML 600 ME 800 ME 900 ME BT 335 36 38 0006160334_202305 ITALIANO...
Page 39: ...I1 I2 BA I4 I3 TBML 600 ME 800 ME 900 ME BT 335 37 38 0006160334_202305 ITALIANO...
Page 73: ...WIRING DIAGRAMS TBML 600 ME 800 ME 900 ME BT 335 33 38 0006160334_202305 ENGLISH...
Page 74: ...TBML 600 ME 800 ME 900 ME BT 335 34 38 0006160334_202305 ENGLISH...
Page 75: ...TBML 600 ME 800 ME 900 ME BT 335 35 38 0006160334_202305 ENGLISH...
Page 76: ...TBML 600 ME 800 ME 900 ME BT 335 36 38 0006160334_202305 ENGLISH...
Page 77: ...I1 I2 BA I4 I3 TBML 600 ME 800 ME 900 ME BT 335 37 38 0006160334_202305 ENGLISH...
Page 79: ......