Example
•
Burner
• Ptc = Pressure measured on port G:
•
Pcc = Back pressure measured in the furnace:
•
Head pressure value without the back pressure in the furnace: P
= Ptc - Pcc
From the diagram, in correspondence of pressure "P", the combusted
thermal input of about "X" can be inferred.
POWER AT START-UP
The standard EN 676 prescribes that for burners with maximum
output above 120 kW the ignition must occur at a reduced power
Pstart
than the maximum power of operation
Pmax
at which the
burner is calibrated.
Pstart
depends on the safety time of the burner equipment; in par
-
ticular:
ts = 2s →
Pstart
≤ 0.5
x
Pmax
.
ts = 3s →
Pstart
≤ 0.333 x
Pmax
.
IMPORTANT
This method permits only an approximate estimate of the
combusted thermal flow rate delivered, for a precise measuring,
refer to gas meter.
Example
if the maximum regulation power of the burner
Pmax
is
equal to 900 kW, it must be:
Pstart
≤ 450 kW where ts = 2s
Pstart
≤ 300 kW where ts = 3s
Check power at ignition
•
Disconnect the flame sensor wire (in this case the burner turns
on and goes into lock-out after the safety time ts).
•
Perform 10 consecutive ignitions and following block.
•
Measure at the meter the amount of gas burned
Qstart
[m³]
and check that
Qstart ≤ Pmax /360
( in m³/h)
Example
Pmax = 90 m³/h (about 900 kW with natural gas)
After 10 ignitions with the related lock out, the gas consumption read
on the meter must be:
Qstart
≤ 90/360 = 0.25 [m³]
If this does not occur, reduce the flow of gas to the ignition through
the brake of the valve.
pr
esapr
ess_TBMLME
G
2
3
20
40
60
80
0
4
100
kWx1000
5
6
7
8
mbar
9
1
0002929600
(Y)
(X)
X : Thermal flow rate (kW x 1000).
Y : Net pressure in gaseous fuel head (mbar).
24 / 38
0006160334_202305
ENGLISH
Summary of Contents for TBML 900 ME
Page 2: ......
Page 35: ...SCHEMI ELETTRICI TBML 600 ME 800 ME 900 ME BT 335 33 38 0006160334_202305 ITALIANO...
Page 36: ...TBML 600 ME 800 ME 900 ME BT 335 34 38 0006160334_202305 ITALIANO...
Page 37: ...TBML 600 ME 800 ME 900 ME BT 335 35 38 0006160334_202305 ITALIANO...
Page 38: ...TBML 600 ME 800 ME 900 ME BT 335 36 38 0006160334_202305 ITALIANO...
Page 39: ...I1 I2 BA I4 I3 TBML 600 ME 800 ME 900 ME BT 335 37 38 0006160334_202305 ITALIANO...
Page 73: ...WIRING DIAGRAMS TBML 600 ME 800 ME 900 ME BT 335 33 38 0006160334_202305 ENGLISH...
Page 74: ...TBML 600 ME 800 ME 900 ME BT 335 34 38 0006160334_202305 ENGLISH...
Page 75: ...TBML 600 ME 800 ME 900 ME BT 335 35 38 0006160334_202305 ENGLISH...
Page 76: ...TBML 600 ME 800 ME 900 ME BT 335 36 38 0006160334_202305 ENGLISH...
Page 77: ...I1 I2 BA I4 I3 TBML 600 ME 800 ME 900 ME BT 335 37 38 0006160334_202305 ENGLISH...
Page 79: ......