Now the equipment is activated again and will automatically
switch to the second stage according to the program set by the
programmer.
•
Start the fuel supply auxiliary circuit and check for its correct
operation, then set pressure to nearly 0,5÷3 bar if such circuit
features a pressure regulator.
•
With the burner operating in the 2nd stage, adjust the quality of
air necessary to ensure efficient combustion.
•
Adjust the combustion so as to obtain a soft light orange flame;
avoid red flames with smoke and white flames with an excess of
air.
DANGER / ATTENTION
The burner must not operate below the stated minimum
capacity, in order to prevent damages to the combustion head
components.
•
During burner ignition, when it passes to the first stage, the air/
gas servomotor takes for a few seconds the burner to a delivery
higher than the first stage.
•
During this transition phase check that the cam (IV) for actuating
the servomotor second stage does not activate.
25 / 50
0006160331_202310
ENGLISH
Summary of Contents for TBML 80 MC
Page 2: ......
Page 45: ...SCHEMI ELETTRICI TBML 50 MC 200 MC 43 50 0006160331_202310 ITALIANO...
Page 46: ...TBML 50 MC 200 MC 44 50 0006160331_202310 ITALIANO...
Page 47: ...45 50 0006160331_202310 ITALIANO...
Page 49: ...TBML 260 MC 360 MC 47 50 0006160331_202310 ITALIANO...
Page 50: ...TBML 260 MC 360 MC 48 50 0006160331_202310 ITALIANO...
Page 51: ...TBML 260 MC 360 MC 49 50 0006160331_202310 ITALIANO...
Page 95: ...WIRING DIAGRAMS TBML 50 MC 200 MC 43 50 0006160331_202310 ENGLISH...
Page 96: ...TBML 50 MC 200 MC 44 50 0006160331_202310 ENGLISH...
Page 97: ...45 50 0006160331_202310 ENGLISH...
Page 99: ...TBML 260 MC 360 MC 47 50 0006160331_202310 ENGLISH...
Page 100: ...TBML 260 MC 360 MC 48 50 0006160331_202310 ENGLISH...
Page 101: ...TBML 260 MC 360 MC 49 50 0006160331_202310 ENGLISH...
Page 103: ......