INSTRUCTIONS FOR DETERMINING THE CAUSE LEADING TO IRREGULARITIES IN THE
OPERATION AND THEIR ELIMINATION
IRREGULARITY
The burner does not start.(The
equipment does not perform the
start up program).
Defective flame with sparks.
Flame not properly shaped with
presence of smoke and soot.
Defective flame, flickering or pro
-
truding from combustion orifice.
POSSIBLE CAUSE
1 Thermostats (boiler or room) or pressure
switches are open.
2 Photoresistor in short circuit.
3 Absence of line voltage, main switch open,
meter switch tripped or absence of line
voltage.
4 Thermostat line not wired according to
diagram or open thermostats.
5 Equipment internal fault.
1 Spraying pressure is too low.
2 Too much combustion air.
3 Nozzle inefficient because dirty or worn.
4 Water in the fuel.
1 Insufficient combustion air flow.
2 Nozzle inefficient because dirty or worn.
3 Nozzle capacity too low with respect to
combustion chamber volume.
4 Combustion chamber unsuitably designed
or too small.
5 Unsuitable refractory coating (it reduces
excessively the space of the flame).
6 Boiler or chimney ducts blocked.
7 Spraying pressure is low.
1 Excessive draught, only when there is an
extractor in the chimney.
2 Nozzle inefficient because dirty or worn.
3 Water in the fuel.
4 Dirty flame disk.
5 Too much combustion air.
6 Air passage between flame disk and diffu
-
ser excessively closed.
REMEDY
1 Raise the thermostats settings, or wait that
the contacts close for natural decrease of
temperature or pressure.
2 Replace it.
3 Activate switches or wait for power to return.
4 Check the connections and thermostats.
5 Replace it.
1 Restore it at the required value.
2 Reduce combustion air
3 Clean or replace.
4 Drain water from the tank using a suitable
pump. Never use the burner pump for this
purpose.
1 Increase combustion air.
2 Clean or replace.
3 Decrease diesel flow rate to suit the chamber
(thermal power will obviously be lower than
necessary) or replace the boiler.
4 Increase nozzle flow by replacing it.
5 Modify it, carefully abiding by the instructions
given by boiler manufacturer.
6 Arrange for cleaning.
7 Restore it at the required value.
1 Adjust the suction fan speed by changing the
pulley diameter.
2 Clean or replace.
3 Drain water from the tank using a suitable
pump. Never use the burner pump for this
purpose.
4 Clean.
5 Reduce combustion air.
6 Correct the position of the combustion head
regulating device.
32 / 56
0006160357_202106
ENGLISH
Summary of Contents for TBML 450LX ME
Page 2: ......
Page 37: ...SCHEMI ELETTRICI TBML 450 ME 510 ME BT 335 35 56 0006160357_202106 ITALIANO ...
Page 38: ...TBML 450 ME 510 ME BT 335 36 56 0006160357_202106 ITALIANO ...
Page 39: ...TBML 450 ME 510 ME BT 335 37 56 0006160357_202106 ITALIANO ...
Page 40: ...TBML 450 ME 510 ME BT 335 38 56 0006160357_202106 ITALIANO ...
Page 41: ...TBML 450 ME 510 ME BT 335 I1 I2 BA I4 I3 39 56 0006160357_202106 ITALIANO ...
Page 42: ...TBML 650 ME 750 ME BT 335 40 56 0006160357_202106 ITALIANO ...
Page 43: ...TBML 650 ME 750 ME BT 335 41 56 0006160357_202106 ITALIANO ...
Page 44: ...TBML 650 ME 750 ME BT 335 42 56 0006160357_202106 ITALIANO ...
Page 45: ...TBML 650 ME 750 ME BT 335 43 56 0006160357_202106 ITALIANO ...
Page 46: ...TBML 650 ME 750 ME BT 335 I1 I2 BA I4 I3 44 56 0006160357_202106 ITALIANO ...
Page 48: ...TBML 450 ME 510 ME BT 340 46 56 0006160357_202106 ITALIANO ...
Page 49: ...TBML 450 ME 510 ME BT 340 47 56 0006160357_202106 ITALIANO ...
Page 50: ...TBML 450 ME 510 ME BT 340 48 56 0006160357_202106 ITALIANO ...
Page 51: ...TBML 450 ME 510 ME BT 340 49 56 0006160357_202106 ITALIANO ...
Page 52: ...I1 I2 BA I4 I3 TBML 450 ME 510 ME BT 340 50 56 0006160357_202106 ITALIANO ...
Page 53: ...TBML 650 ME 750 ME BT 340 51 56 0006160357_202106 ITALIANO ...
Page 54: ...TBML 650 ME 750 ME BT 340 52 56 0006160357_202106 ITALIANO ...
Page 55: ...TBML 650 ME 750 ME BT 340 53 56 0006160357_202106 ITALIANO ...
Page 56: ...TBML 650 ME 750 ME BT 340 54 56 0006160357_202106 ITALIANO ...
Page 57: ...I1 I2 BA I4 I3 TBML 650 ME 750 ME BT 340 55 56 0006160357_202106 ITALIANO ...
Page 93: ...WIRING DIAGRAMS TBML 450 ME 510 ME BT 335 35 56 0006160357_202106 ENGLISH ...
Page 94: ...TBML 450 ME 510 ME BT 335 36 56 0006160357_202106 ENGLISH ...
Page 95: ...TBML 450 ME 510 ME BT 335 37 56 0006160357_202106 ENGLISH ...
Page 96: ...TBML 450 ME 510 ME BT 335 38 56 0006160357_202106 ENGLISH ...
Page 97: ...TBML 450 ME 510 ME BT 335 I1 I2 BA I4 I3 39 56 0006160357_202106 ENGLISH ...
Page 98: ...TBML 650 ME 750 ME BT 335 40 56 0006160357_202106 ENGLISH ...
Page 99: ...TBML 650 ME 750 ME BT 335 41 56 0006160357_202106 ENGLISH ...
Page 100: ...TBML 650 ME 750 ME BT 335 42 56 0006160357_202106 ENGLISH ...
Page 101: ...TBML 650 ME 750 ME BT 335 43 56 0006160357_202106 ENGLISH ...
Page 102: ...TBML 650 ME 750 ME BT 335 I1 I2 BA I4 I3 44 56 0006160357_202106 ENGLISH ...
Page 104: ...TBML 450 ME 510 ME BT 340 46 56 0006160357_202106 ENGLISH ...
Page 105: ...TBML 450 ME 510 ME BT 340 47 56 0006160357_202106 ENGLISH ...
Page 106: ...TBML 450 ME 510 ME BT 340 48 56 0006160357_202106 ENGLISH ...
Page 107: ...TBML 450 ME 510 ME BT 340 49 56 0006160357_202106 ENGLISH ...
Page 108: ...I1 I2 BA I4 I3 TBML 450 ME 510 ME BT 340 50 56 0006160357_202106 ENGLISH ...
Page 109: ...TBML 650 ME 750 ME BT 340 51 56 0006160357_202106 ENGLISH ...
Page 110: ...TBML 650 ME 750 ME BT 340 52 56 0006160357_202106 ENGLISH ...
Page 111: ...TBML 650 ME 750 ME BT 340 53 56 0006160357_202106 ENGLISH ...
Page 112: ...TBML 650 ME 750 ME BT 340 54 56 0006160357_202106 ENGLISH ...
Page 113: ...I1 I2 BA I4 I3 TBML 650 ME 750 ME BT 340 55 56 0006160357_202106 ENGLISH ...
Page 115: ......