M039320CA  Rel 0.1  06/2017

BURNERS - BRUCIATORI - BRULERS - BRENNER - QUEMADORES - 

ГОРЕЛКИ

LMV2x

Microprocessor controlled

gas burners  

MANUAL OF INSTALLATION - USE - MAINTENANCE

LX60 - LX65 - LX72

Summary of Contents for LX60

Page 1: ...M039320CA Rel 0 1 06 2017 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES LMV2x Microprocessor controlled gas burners MANUAL OF INSTALLATION USE MAINTENANCE LX60 LX65 LX72...

Page 2: ...n a suitable room with ventilation openings complying with the requirements of the regulations in force and sufficient for good combustion z Only burners designed according to the regulations in force...

Page 3: ...EC Gas Directive 2014 35 UE Low Tension Directive 2014 30 UE Electromagnetic compatibility Directive 2006 42 EC Machinery Directive Harmonized standards UNI EN 676 Automatic forced draught burners for...

Page 4: ...ype Characteristics and test methods Industrial burners European directives 2009 142 EC Gas Directive 2014 35 UE Low Tension Directive 2014 30 UE Electromagnetic compatibility Directive 2006 42 EC Mac...

Page 5: ...e versions PR Progressive MD Fully modulating 4 BLAST TUBE S Standard L Extended 5 DESTINATION COUNTRY see data plate 6 BURNER VERSION A Standard Y Special 7 EQUIPMENT 1 2 valves gas proving system 8...

Page 6: ...rating temperature C 10 50 Storage Temperature C 20 60 Working service Intermittent BURNERS LX65 M 0 50 LX65 M 0 65 Output min max kW 245 760 Fuel Natural gas Category see next paragraph Gas rate min...

Page 7: ...ressure 360mbar with Dungs MBDLE Maximum gas pressure 500mbar with Siemens VGD Minimum gas pressure see gas curves GAS CATEGORY COUNTRY I2H AT ES GR SE FI IE HU IS NO CZ DK GB IT PT CY EE LV SI MT SK...

Page 8: ...C CC D E F G H J K L M N O min O max P Q R S U V W Y Z LX60 0 40 40 1026 1206 99 252 432 314 736 298 812 500 312 185 204 210 240 344 M10 269 190 190 190 439 112 327 444 x 464 162 120 LX60 0 50 50 102...

Page 9: ...30 216 250 233 533 130 403 565 313 548 162 155 DN A S A L AA B S B L BB C CC D E F G H J K L M N Omin Omax P Q R S U V W Y Z LX72 MD 0 40 50 1139 1224 130 300 385 373 803 316 832 500 332 219 249 208 3...

Page 10: ...ambient temperature at 15 C NOTE The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory tests but does not represent the regulation r...

Page 11: ...ue must be lower or equal to the pgas value calcula ted before GAS PRESSURE mbar LX60 M 40 Gas rate Stm3 h LX60 M 50 65 Gas rate Stm3 h GAS PRESSURE mbar LX65 Gas rate Stm3 h LX72 Gas rate Stm3 h Caut...

Page 12: ...the combustion chamber 3 Gas pressure outlet on the butterfly valve 4 Differential pressure gauge Measuring the gas pressure in the combustion head In order to measure the pressure in the combustion h...

Page 13: ...sure in combustion head mbar LX60 Stm3 h LX65 Stm3 h Gas pressure in combustion head mbar LX72 Stm3 h WARNING the diagrams refers to natural gas For different type of fuel please refer to the paragrap...

Page 14: ...xing nuts according to the next picture 8 After fitting the burner to the boiler ensure that the gap between the blast tube and the refractory lining is sealed with appropriate insulating material cer...

Page 15: ...lication involved To correctly match the burner to the boiler verify the type of the blast tube Verify the necessary input and the pressure in combustion chamber are included in the burner performance...

Page 16: ...governor pressure switch gas leakage pressure switch PGCP Gas train with valves group VGD with built in gas pressure governor gas leakage pressure switch PGCP 1 Filter 6 Butterfly valve 2 Pressure sw...

Page 17: ...insert MB DLE note position of O rings see Fig 10 3 tighten screws A B C and D Fig 8 Fig 9 accordind to the mounting positions Fig 11 4 after installation perform leakage and functional test 5 disasse...

Page 18: ...e tight z make certain that the O rings and gaskets between the flanges and the double gas valve are fitted z Connect the reference gas pipe TP in figure 8mm external size pipe supplied loose to the g...

Page 19: ...e switches Gas Filter if provided The gas filters remove the dust particles that are present in the gas and prevent the elements at risk e g burner valves counters and regulators from becoming rapidly...

Page 20: ...nal X3 04 4 in case of LMV2x LMV3x LMV5x LME7x on the board and the earth terminal an RC Siemens RC466890660 filter must be inserted For LMV5 control box please refer to the clabeling recommendations...

Page 21: ...ER OPEN OR DISMANTLE ANY COMPONENT OF THE MACHINE EXCEPT FOR ITS MAINTENANCE TO SECURE THE MACHINE ACT ON THE ISOLATOR SWITCH IN CASE OF ANOMALIES THAT REQUIRED A SHUT DOWN OF THE BURNER IT S POSSIBLE...

Page 22: ...g pre purgue phase G Low flame operation indicator light H Ignition tranformer operation indicator light I Valve in operation indicator light for EV2 L Valve in operation indicator light for EV1 M Ind...

Page 23: ...elow The keys functions are the following WARNING During commissioning operations do not let the burner operate with insufficient air flow danger of formation of carbon monoxide if this should happen...

Page 24: ...the curve adjustments Keys ESC By pressing and at the same time the ESCAPE function is perfomed to enter a lower level menu Bloc Descrizione Description Password 100 Informazioni generali General OEM...

Page 25: ...e ignition transformer OFF t42 preignition time OFF Ph44 t44 intervallo 1 t44 interval 1 Ph50 TSA2 secondo tempo sicurezza TSA2 2nd safety time Ph52 t52 intervallo 2 t52 interval 2 Ph60 Funzionamento...

Page 26: ...ess the enter InFo key 3 then il will show the first code 167 flashing on the right side it will show the data entered By pressing or it is possible to scroll up or down the parameter list 4 If a dot...

Page 27: ...End message will flash 10 Press InFo for more than three seconds or for more than three seconds orto return to the normal display If a message like the one below is shown during operation it means th...

Page 28: ...f phases Example Error code 111 diagnostic code 0 To reset press InFo for a second Record the codes and check the Error List to find the type of faults Service level To enter the Service mode press In...

Page 29: ...y pressinf or it is possible to scroll up down the parameter list 2 Once the last parameter is accessed 143 by pressing the End message will blink 3 Press InFo for more than three seconds or for more...

Page 30: ...ver C By screwing down the pressure is increased and by unscrewing it is reduced Note the screw VSB must be removed only in case of replacemente of the coil Fig 23 Fig 24 Key 1 Electrical connection f...

Page 31: ...er 2 if the maximum pressure switch is mounted upstreaam the gas valves measure the gas pressure in the network when flame is off by means of the adjusting ring nut VR set the value read increased by...

Page 32: ...the pressure value until the burner stops z Slowly fully open the manual cutoff valve z Refit the transparent plastic cover on the pressure switch Adjusting the maximum gas pressure switch when provi...

Page 33: ...if necesssary z Remove and clean the combustion head z Examine and clean the ignition electrodes adjust and replace them if necessary z Examine and clean the detection electrode photoelement according...

Page 34: ...using any force and fasten 5 Perform leakage and functional test pmax 360 mbar 6 Pay attention that dirt does not fall inside the valve Removing the filter in the MULTIBLOC DUNGS MB DLE 415 420 B01 1...

Page 35: ...PART IV MAINTENANCE 35 Fig 28 Fig 29 Fig 30 B A C D E...

Page 36: ...sition the manifold G and pull out the complete group as shown in figure Note for the subsequent assembly carry out the above described operations in the reverse order checking the correct position of...

Page 37: ...cables 3 loose the screws of the electrodes VB 4 remove the ignition electrodes and replace them paying attention to the measures shown in figure Adjust the electrodes position according to the quote...

Page 38: ...top To stop the burner in the seasonal stop proceed as follows 1 turn the burner main switch to 0 Off position 2 disconnect the power mains 3 close the fuel valve of the supply line Burner disposal In...

Page 39: ...PART IV MAINTENANCE 39 WIRING DIAGRAMS Refer to the attached wiring diagrams WARNING 1 Electrical supply 230V 400V 50Hz 3N a c 2 Do not reverse phase with neutral 3 Ensure burner is properly earthed...

Page 40: ...AS z z MAXIMUM GAS PRESSURE SWITCH DEFECTIVE z z THERMOSTATS PRESSURE SWITCHES DEFECTIVES z z z OVERLOAD TRIPPED INTERVENTION z AUXILIARIES FUSE INTERRUPTED z DEFECTIVE CONTROL BOX z z z z z DEFECTIVE...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...a L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors an...

Page 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...

Page 46: ...900 Process data 32 Actuators references 33 Gas proving system 33 Air fuel curve points 33 COMMISSIONING THE BURNER 34 Warm setting 38 Cold setting 39 BURNER STARTUP WITH LMV2x ALREADY PROGRAMMED 40...

Page 47: ...CTIONS FOR BURNERS z The burner should be installed in a suitable room with ventilation openings complying with the requirements of the regulations in force and sufficient for good combustion z Only b...

Page 48: ...ditions such as the development of toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 2009 142 EC Gas Appliances Directive 2006 95 EC on low voltage Directi...

Page 49: ...apparatus EN 50165 Electrical equipment of non electric appliances for household and similar purposes Safety requirements UNI EN 746 2 Industrial thermoprocessing equipment Burner data plate For the...

Page 50: ...forms all the burner control functions and of the Siemens AZL local programming unit that interfaces the system with the user Keys 1 Burner 2 AZL2 3 Air actuator 4 Fuel actuator 5 LMV2 User interface...

Page 51: ...ice mode Info and Enter keys Used for Info and Service menues Used as Enter key in the setting modes Used as Reset key in the burner operation mode Used to enter a lower level menu Key Used to decreas...

Page 52: ...8 Parameters level heating engineer...

Page 53: ...ription Password 000 Internal parameters OEM Service 100 Informazioni generali General OEM Service Info 200 Controllo bruciatore Burner control OEM Service 300 Controllo bruciatore solo LMV26 Burner c...

Page 54: ...kup data set Service Info Param Descrizione Description Password LMV20 LMV27 LMV26 LMV37 102 Data produzione in gg mm aa Identification date yy mm dd Service Info x x x 103 Numero identificativ Identi...

Page 55: ...ed OEM Service x x 145 Indirizzo dispositivo per Modbus Device address for Modbus OEM Service x x 146 Velocit di trasmissione per Modbus Baud rate for Modbus OEM Service x x 147 Parit per Modbus Parit...

Page 56: ...erci zio azzerabile da Service Fuel 1 Operation hours resettable Service Info x 174 Fuel 1 secondo combustibile Numero di partenze azzerabile da Service Fuel 1 Number of startups resettable Service In...

Page 57: ...e fuel train modula ting multistage actuators etc __ undefined delete curves 1 gas direct ignition G mod 2 ignition by gas pilot connected between the two gas solenoid valves EV1 EV2 Gp1 mod 3 ignitio...

Page 58: ...x x x 210 Allarme impedimento avviamento 0 non attivo 1 attivo Alarm in the event of start prevention 0 deactivated 1 activated OEM Service x x x 211 Tempo aumento giri ventilatore valore fab brica 2...

Page 59: ...nge impostazione 20s 60min Gas Prepurge time default value 20s range 20s 60min OEM Service x x x 226 Gas tempo di preaccensione valore fab brica 2s range impostazione 0 2s 60min Gas Preignition time d...

Page 60: ...ivo 1 esso modificabile solo su LMV37 Dal punto di vista della sicurezza il funzionamento continuo valido esclusiva mente per bruciatori di gas con elettrodo di rilevazione Gas Forced intermittent ope...

Page 61: ...Postpurge time 3 abortion with load controller LR ON OEM Service x x x 261 Olio sonda rilevazione fiamma attivo valore fabbrica 0 0 QRB QRC 1 ION QRA Oil active detector flame evaluation default value...

Page 62: ...0 inactive 1 active from phase 38 2 active from safety time TSA OEM Service x x 277 Olio Pressostato olio di massima ingresso POC 0 inattivo 1 pressostato olio di massima 2 POC Oil Pressure switch max...

Page 63: ...lvole EV1 EV2 del gas regolazione pneumatica Gp1 mod pneu 9 accensione tramite pilota gas con attacco a monte dell elettrovalvola EV1 del gas regolazione pneumatica Gp2 mod pneu 10 olio modulante con...

Page 64: ...ore fabbrica 1 0 QRB QRC 1 ION QRA Fuel 1 Gas active detector flame evalua tion default value 1 0 QRB QRC 1 ION QRA OEM Service x 322 Combustibile 1 Gas Preventilazione valore fabbrica 1 1 attivo 0 no...

Page 65: ...Intervallo 2 valore fabbrica 2s range impostazione 0 2s 60min Fuel 1 Gas Interval 2 default value 2s range 0 2s 60min OEM Service x 333 Combustibile 1 Gas Tempo postcombu stione valore fabbrica 8s ra...

Page 66: ...t filling time default value 3s range 0 2s 10s OEM x 345 Combustibile 1 Gas tempo test pressione gas valore fabbrica 10s range imposta zione 0 2s 60s Fuel 1 Gas proving test time gas pres sure default...

Page 67: ...mbustibile 1 Olio tempo di risposta a cadute di pressione entro TSA1 e TSA2 valore fabbrica 1 8s range imposta zione 0 2s 14 8s Fuel 1 Oil time to respond to pressure faults in TSA1 and TSA2 default v...

Page 68: ...censione corta Ph38 fase pro gramma 38 1 preaccensione lunga con ventilatore Ph22 fase programma 22 Fuel 1 Oil time oil ignition default value 1 0 short preignition Ph38 progr phase 38 1 long preignit...

Page 69: ...ting the cur ves OEM Service x x x 403 Curve controllo inverter F A si accede alla lista dei punti da impostare da P0 a P9 con sultare paragrafo Impostazione curve Ratio control curves VSD curve setti...

Page 70: ...repurge speed 100 Index 2 postpurge speed 50 OEM Service x x 504 Combustibile 1 Posizione servocomando combustibile in assenza di fiamma no flame Indice 0 posizione di sosta 0 Indice 1 posizione preve...

Page 71: ...di carico per modulazione valore fabbrica n d range imposta zione 20 100 Lower load limit default value n d range 20 100 OEM Service x x x 546 Percentuale massima di carico per modula zione valore fa...

Page 72: ...0 combustibile Indice 1 aria Tolerance limit of position monitoring 0 1 Index 0 fuel Index 1 air OEM Service x x x 608 Combustibile 1 Impostazione punto di riferi mento Indice 0 combustibile Indice 1...

Page 73: ...top SQN1 3 both OEM x 613 Tipo di servocomando Indice 0 combustibile Indice 1 aria 0 5s 90 1Nm 1 2Nm 3Nm 1 10s 90 6Nm 2 17s 90 10Nm Type of actuator Index 0 fuel Index 1 air 0 5 s 90 1Nm 1 2Nm 3Nm 1 1...

Page 74: ...tion of analog output default value 0 0 DC 0 10 V 1 DC 2 10 V 2 DC 0 2 10 V OEM Service LMV27 x x ATTENTION as for SQM3x actuators set the direction according to the acutator function As far as SQN1x...

Page 75: ...ror history 701 725 02 diagnostic code Service Info Storico errori 701 725 03 classe errore Error history 701 725 03 error class Service Info Storico errori 701 725 04 fase Error history 701 725 04 ph...

Page 76: ...Active load source OEM Service 945 Solo con LMV26 Combustibile attuale 0 combustibile 0 1 combustibile 1 Actual fuel 0 fuel 0 1 fuel 1 Service Info 947 Risultato interrogazione contatti codifica bit...

Page 77: ...a leakage test designed to detect leaking gas valves and if necessary to pre vent the valves from opening or ignition from being switched on Lockout is initiated When performing valve proving the gas...

Page 78: ...2x already programmed At the first LMV startup the AZL display will show It means that the unit was never set or that no mode was chisen or that some parameters have to be set furthert Push F fuel and...

Page 79: ...l elettrov EV1 del gas Gp2 mod 4 accensione a gasolio modul Lo mod 5 accens a gasolio bistadio Lo 2 stage 6 accens a gasolio tristadio Lo 3 stage Burner operating mode fuel train mod multi stage actua...

Page 80: ...e fuel actuator 0F until the requested value is reached for example 12 15 see below for the ignition point or press F and to decrease the angle To set the air damper opening angle 0A in the ignition p...

Page 81: ...er is operating warm setting by pressing the ENTER InFo or while the burner is in stand by mode cold setting by pressing ENTER CAUTION at the first burner adjustment it is recommended to set the maxim...

Page 82: ...ugh the flue analyser Keep the air excess inside normal figures from 3 to 7 residual O2 operating by means for the air damper servomotor Keep increasing the air damper opening and then the gas throttl...

Page 83: ...t before end by pressing ESC or for a faulty shutdown the message OFF UPr Start preven tion will be diplayed until all the curvepoints will be set Note2 if the gas flow rate at high flame point maximu...

Page 84: ...e than 5 seconds to process the curve downwards The curve is then a straight line go on checking the combustion values point by point change them if necessary and in case linearise the curve again Bef...

Page 85: ...e burntime Ph72 travelling to postpurging Ph74 postpurge countdown is displayed Press ESC the parameter 546 Setting the maximum load is displayed Then press to exit the programming mode The display wi...

Page 86: ...n Longer or shorter pushes on the button do not produce a reset so that the system maintains the lockout position Timeout for menu operation The time for automatically leaving the parameter setting le...

Page 87: ...levels By means of a proper use of the keys it is possible to enter the various level parameters as shown in the following flow chart The burner and consequently the LMV2x are factory set the air and...

Page 88: ...nd go back to the flashing number The Info level shows some basic parameters as 5 Example choose parameter 102 to show the date the display shows parameter 102 flashing on the left and characters _ _...

Page 89: ...h another message Diagnostic code in the example diagnostic code 3 Record the codes and find out the fault in the Error table To perform the reset press InFo for one second The unit displays an event...

Page 90: ...ht By pressinf or it is possible to scroll up down the parameter list 2 Once the last parameter is accessed 143 by pressing the End message will blink 3 Press InFo for more than three seconds or for m...

Page 91: ...ignition time OFF Ph44 t44 intervallo 1 t44 interval 1 Ph50 TSA2 secondo tempo sicurezza TSA2 2nd safety time Ph52 t52 intervallo 2 t52 interval 2 Ph60 Funzionamento 1 stazionario Operation 1 stationa...

Page 92: ...ess ENTER until the display will show with the button go to the group 000 of the parameters and press with the buttons and go to 050 parameter press the disply show press again with the button select...

Page 93: ...uttons by pressing enter to confirm iWith the buttons go to the group 000 of the parameters press end select the 050 parameter press the disply show with the button the display shows press again with...

Page 94: ...50 ERROR CODE TABLE...

Page 95: ...51...

Page 96: ...52...

Page 97: ...53...

Page 98: ...54...

Page 99: ...55...

Page 100: ...56...

Page 101: ...57...

Page 102: ...58...

Page 103: ...59...

Page 104: ...60...

Page 105: ...61...

Page 106: ...62...

Page 107: ...63...

Page 108: ...64...

Page 109: ...L PE QRB C N ION QRB C X75 1 X10 05 1 X10 06 1 X3 02 1 PLUFT FLAMME P L PE N L 2 3 L X5 03 1 X8 04 1 X8 02 1 X5 03 X10 05 X7 01 X8 04 X8 02 X75 X10 06 X3 02 X3 04 N PE L 1 1 1 1 1 1 1 1 1 QRA QRA QRA...

Page 110: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...

Page 111: ...tion speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply 4 Feedback signal 3 PWM Pulse Width Modulation speed output 2 GND signal reference 1 External supply 24V DC ConnectorX75 Con...

Page 112: ...dulation speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply ConnectorX75 ConnectorX64 ConnectorX74 2 Fuel meter input 1 Supply fuel meter ConnectorX5 02 Connections Pmax 4 Feedback...

Page 113: ......

Page 114: ......

Page 115: ......

Page 116: ...and data subject to change Errors and omissions excepted C I B UNIGAS S p A Via L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail...