AIR REGULATION ON THE COMBUSTION HEAD
The combustion head is equipped with a regulation device that
makes it possible to open or close the air passage between the
disk and the head. Closing the passage increases the pressure
upstream of the disk also with low flow rates. The high speed and
turbulence of the air provides for its greater penetration into the
fuel and therefore an excellent mixture and flame stability. High air
pressure upstream of the disk may be necessary to prevent flame
fluctuations, this is particularly essential when the burner works
on the furnace that is pressurised and/or at a high thermal load.
The combustion head closing device must be set to a position in
which, behind the disc, there is always a very high air pressure
value. When the burner operates at maximum delivery, adjust the
head air closure, in such a way as to require a considerable air flow
damper opening. Therefore start the regulation with the device that
closes the air on the combustion head in an intermediate position,
igniting the burner for an indicative regulation as explained above.
Move the combustion head forward or backward so as to have an
air flow suitable for the delivery.
CAUTION / WARNINGS
The above adjustments are only indicative; position the
combustion head according to the characteristics of the
furnace.
X = Head-disk distance; adjust distance X following the
instructions:
• Loosen the screw (1)
•
Turn screw (2) to position the combustion head (3), referring
to index (4)
•
Adjust the distance (x) between the minimum and maximum
according to the indications in the table
BURNER
X
Value indicated by
index 4
TBML 200 MC / ME
110 ÷ 150
4 ÷ 1
TBML 260 MC / ME
106 ÷ 156
5 ÷ 1
TBML 360 MC / ME
98 ÷ 136
4 ÷ 1
Summary of Contents for 56495410
Page 2: ......
Page 48: ...ITALIANO 46 54 0006081544_201907 SCHEMI ELETTRICI...
Page 49: ...ITALIANO 47 54 0006081544_201907...
Page 50: ...ITALIANO 48 54 0006081544_201907...
Page 52: ...ITALIANO 50 54 0006081544_201907...
Page 53: ...ITALIANO 51 54 0006081544_201907...
Page 54: ...ITALIANO 52 54 0006081544_201907...
Page 56: ...ITALIANO 54 54 0006081544_201907...
Page 102: ...ENGLISH 46 54 0006081544_201907 WIRING DIAGRAMS...
Page 103: ...ENGLISH 47 54 0006081544_201907...
Page 104: ...ENGLISH 48 54 0006081544_201907...
Page 106: ...ENGLISH 50 54 0006081544_201907...
Page 107: ...ENGLISH 51 54 0006081544_201907...
Page 108: ...ENGLISH 52 54 0006081544_201907...
Page 110: ...ENGLISH 54 54 0006081544_201907...
Page 111: ......