![Baltimore Aircoil Company TrilliumSeries TRF Operation & Maintenance Manual Download Page 98](http://html1.mh-extra.com/html/baltimore-aircoil-company/trilliumseries-trf/trilliumseries-trf_operation-and-maintenance-manual_3617020098.webp)
TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
Alarms & Troubleshooting
Page | 98
11. Alarms & Troubleshooting
All the possible alarms as well as troubleshooting recommendations are listed in
. Unit alarm codes
are listed in
and fan alarm codes are listed in
Parameter
Condition
Trigger Criteria
The unit will issue the alarm when all the following are true:
• Pump X Contact is On for 10 consecutive seconds
• Pump X Current Switch is False for 3 consecutive seconds
Release Criteria
The unit will release the alarm when any of the following are true:
• Pump X Contact is Off
• Pump X Contact is On AND Pump X Current Switch is True
Troubleshooting
• Check Pump X and wiring
• Check Pump X Current Switch and wiring
General Alarm DO
True
Effect
If this alarm occurs 3 times, Pump X will be locked out and the alarm must be
cleared via the HMI.
Table 37. Pump X No Current Alarm
Parameter
Condition
Trigger Criteria
The unit will issue the alarm when the following is true:
• 3 Pump X No Current Alarms have occurred
Release Criteria
The unit will release the alarm when the following is true:
• Pump X Lockout is
cleared
Troubleshooting
• Check Pump X and wiring
• Check Pump X Current
Switch and wiring
General Alarm DO
True
Effect
Pump X will be locked out from starting.
Table 38. Pump X Lock Out Alarm
Parameter
Condition
Trigger Criteria
The unit will issue the alarm when any of the following are true:
• Control Type = LFT Ctrl AND
Fluid Type = Water AND Leaving Fluid Temperature
≤ 10 °C for 3 consecutive seconds
• Control Type = LFT Ctrl AND
Fluid Type = Glycol AND Leaving Fluid Temperature
≤ 7.2 °C for 3 consecutive seconds
Release Criteria
The unit will release the alarm when any of the following are true:
• Control Type = LFT Ctrl AND
Fluid Type = Water AND Leaving Fluid Temperature
> 13 °C for 3 consecutive seconds
• Control Type = LFT Ctrl AND
Fluid Type = Glycol AND Leaving Fluid Temperature
> 10.2 °C for 3 consecutive seconds
• Control Type ~= LFT Ctrl
Troubleshooting
• Check Leaving Fluid Temperature sensor installation
• Check Leaving Fluid Temperature sensor and wiring
General Alarm DO
True
Effect
Emergency Flag = True
Table 39. Low Leaving Fluid Temperature Alarm