TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
User Interface
Page | 73
Parameter
Description
Makeup Valve X
Force either make-up valve on or off.
Pump X Contact
Force either pump on or off.
Drain Valve
Force the drain valve open or closed.
General Alarm
Force the general alarm contact on or off.
Table 26. I/O Menu, Manual Parameters
Alarms
This menu allows a user to read and clear alarms. The alarm menu is shown in
All active alarms are displayed with a red font; inactive alarms are displayed in a black font. For a detailed overview of the
different alarms, see
Section 11. Alarms & Troubleshooting
Page 98
Figure 61. Alarms Menu
Parameter
Description
Download to USB
Pressing the Download button will verify if a portable USB storage device is present
in the USB bulkhead located inside the HMI enclosure and download the alarm log
(a progress bar will indicate the status of the process).
Information
Pressing the Information button will display the alarm detail page of the selected
alarm as shown in
Acknowledge Current
P
ressing the ‘single checkmark’ will clear the selected alarm
.
Acknowledge All
Pressing the ‘multi
-
checkmark’ will clear all active alarms and change the text from
a red to a black font. A pop-up window will ask for a confirmation first.
Table 27. Alarm Menu Parameters