12.
Using zip cable ties secure cables to the fan and motor support channels. Ensure the cable is routed in a U-shape as
shown in
Figure 21. Fan and Motor Assembly Cable Routing
13.
Reinstall cable gland caps with a tightening torque of 4 ± 0.6 Nm. Make sure all cable glands not in use are fitted
with dummy plugs. Proper installation of cable gland caps is critical to maintain weatherproof rating of the unit. If the
above procedure is not followed, damage due to water ingress will occur.
14.
Inspect the terminal box cover gasket and reinstall the terminal box cover with a tightening torque of 3.5 ± 0.5 Nm as
shown in
. Proper installation of the terminal box cover is critical to maintain weatherproof rating of the unit.
If the above procedure is not followed, damage due to water ingress will occur.
15.
Reinstall the fan cover plate as shown in
16.
Follow section