TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
User Interface
Page | 53
Figure 38. Setpoints Menu, Customer Input Control
Parameter
Description
Operating Mode:
Default
Utilizes factory set operating variables that provides a balance of water and energy
savings. See
Table 12. Operating Mode Parameters
for more information.
Operating Mode:
Energy Saver
Energy Saver mode will enter adiabatic operation more quickly than Default or
Water Saver Operating Modes resulting in lower fan power energy consumption.
See
Table 12. Operating Mode Parameters
Operating Mode: Water
Saver
Water Saver mode will stay in dry operation longer than Default or Energy Saver
Operating Modes resulting in lower water consumption. See
Signal Type
Defines the type of input signal. This can be set to either 4-20mA, 0-10V, 10-0V or
BMS 0-100%. The current signal is supplied to input card EL3014 channel 2 or
contacts X7:27 and X7:28. The voltage signal is supplied to input card EL3174
channel 1 or cont
acts X7:17 and X7:18. The BMS signal refers to the “CIFanCMD”
variable in
Table 65. BMS Communication Points List
Leaving Fluid Temp
Setpoint
Set-point for the fluid outlet temperature
Control Range
Allowed offset in leaving fluid temperature set point before changing
stages/operating modes. For example, allows leaving fluid temperature to rise
above leaving fluid temp setpoint by this control range before changing to adiabatic
mode.
Adiabatic Switchpoint
Ambient temperature at which adiabatic operation becomes possible. See
Page 13
Run Authorization Type
Source signal to switch the unit between stand-by and active. This can be set to
either HMI, digital input or BMS. HMI refers to the button on the top left of the
screen, digital input refers to input card EL1008 channel 6 or contacts X5:7 and
X5:8 on the terminal strip, BMS refers to the “BMSrunEn” variable in
. The HMI button is always taken into account to
enable the unit to run (also when the type is set to digital input or BMS).
Table 11. Setpoints Menu, Leaving Fluid/Customer Input Control Parameters