![Baltimore Aircoil Company TrilliumSeries TRF Operation & Maintenance Manual Download Page 14](http://html1.mh-extra.com/html/baltimore-aircoil-company/trilliumseries-trf/trilliumseries-trf_operation-and-maintenance-manual_3617020014.webp)
TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
General Information
Page | 14
Load Limiting Modes
Night Quiet
Night Quiet load limiting mode will reduce sound levels of the unit overnight. When active, the Night Quiet feature limits the
maximum fan speed and uses a Night Quiet specific dry switchpoint. This will allow the cooler to run adiabatically at lower
outside air temperatures to maintain capacity. The Night Quiet feature can be activated on the touchscreen, through the BMS,
or by a schedule, so that the user can define a start time on one day and a stop time on the next day. All times are in a 24-hour
format.
Night Dry
Night Dry load limiting mode will prevent adiabatic operation of the unit overnight and can be activated by a schedule, so that
the user defines a start time on one day and a stop time on the next day. All times shall be in 24-hour format.
Schedule Dry
Schedule Dry load limiting mode prevents adiabatic operation during the day and can be activated by a schedule, so that the
user defines a start time on one day and a stop time on the same day. All times shall be in 24-hour format.
Maintenance Modes
Coil Clean
Coil Clean is a scheduled maintenance mode that will remove loose debris from the coil surface, ensuring maximum energy
efficiency. Coil clean reverses fan rotation and airflow while opening the make-up and drain valve if the outside air temperature
is greater than 40°F (4°C) to flush debris down the drain.
Pad Clean
Pad Clean is a scheduled maintenance mode that removes loose debris from the adiabatic pre-cooler pad surface, ensuring
maximum energy efficiency. Pad clean will open the make-up and drain valves to flush the pads with clean water.
Complete Drain and Dry
Complete Drain and Dry is a scheduled maintenance mode that fully drains the sump and dries out the adiabatic pre-cooler
pads.
Warranty
Please refer to the Terms and Conditions in the submittal package applicable to and in effect at the time of the sale/ purchase
of these products.