TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
User Interface
Page | 54
Parameter
Operating Mode
Default
Energy Saver
Water Saver
Control Range
3.6°F (2.0°C)
0.9°F (0.5°C)
10.0°F (5.5°C)
Adiabatic Switchpoint
X
lowers current setpoint
by 10.0°F (5.5°C)
X
Stage Timer
120 seconds
60 seconds
300 seconds
Table 12. Operating Mode Parameters
Basin Water Quality Menu
The Basin Water Quality menu shown in
allows a user to adjust parameters shown in
Figure 39. Setpoints Menu, Basin Water Quality Page 1 of 2