TrilliumSeries™ Adiabatic
Cooler - TRF Operation & Maintenance Manual
–
Recommended Maintenance Intervals
Page | 6
1. Recommended Maintenance Intervals
1
Recommended service intervals are the minimum for typical installations. Harsh environmental conditions may dictate more frequent servicing.
2
Do not attempt to remove the adiabatic pre-cooler pads wet to prevent excessive degradation.
Inspect and clean as necessary
[1]
:
Start-Up
Monthly
Quarterly
Semi
Annually
Annually
Inspect general condition of the unit and check unit for unusual noise or vibration
✔️
✔️
Inspect sump
✔️
✔️
Inspect water distribution system
✔️
✔️
Clean sump strainers & recirculation pumps
✔️
✔️
Inspect water level float switches
✔️
✔️
Inspect adiabatic pre-cooler pads
[2]
✔️
✔️
Check operation of make-up valves and drain valve
✔️
✔️
Inspect the pressure reducing valve
✔️
Check operation of pumps
✔️
✔️
Check operation of water level float switches
Inspect coil
✔️
✔️
Run coil clean maintenance mode
✔️
Inspect unit finish
✔️
Mechanical equipment system
[1]
:
Start-Up
Monthly
Quarterly
Semi
Annually
Annually
Check motor voltage and current
✔️
✔️
Check general condition of the fan(s)
✔️
✔️
Check fan cycling, smooth operation
✔️
✔️
✔️
✔️
✔️