14
4
Installation and connection (continued)
4.5
Shielding and cable routing
Defined ground!
The magnetic encoder system and the control
cabinet must be at the same ground potential.
Shielding/cable routing
To ensure electromagnetic compatibility (EMC), observe
the following:
– The cable shield must be grounded on the controller
side, i.e. connected to the protective earth conductor.
– When ducting the cable between the sensor, controller,
and power supply, it is important to avoid going near
high voltage cables due to interferences.
Stray noise from AC harmonics (e.g. from phase angle
controls or frequency converters) are especially critical
and the cable shield offers very little protection against
this.
– The cable must be routed tension-free.
Magnetic fields
The magnetic encoder system is a magnetically coded
system.
Ensure sufficient separation between the magnetic
encoder system and strong external magnetic fields.
Cable length
The maximum cable length according to the DRIVE-CLiQ
specification is 100 m.
Observe voltage drop in cable!
The nominal voltage on the BML must not be
undercut.
BML SGA-AEZ1-LZZZ- _ _ _1- _ _ _ _
Absolute magnetic encoder system
english
Summary of Contents for BML SGA-AEZ1-LZZZ 1 Series
Page 2: ...www balluff com...
Page 3: ...deutsch Betriebsanleitung BML SGA AEZ1 LZZZ _ _ _1 _ _ _ _...
Page 4: ...www balluff com...
Page 29: ...english User s Guide BML SGA AEZ1 LZZZ _ _ _1 _ _ _ _...
Page 30: ...www balluff com...
Page 55: ...fran ais Notice d utilisation BML SGA AEZ1 LZZZ _ _ _1 _ _ _ _...
Page 56: ...www balluff com...
Page 81: ...italiano Manuale d uso BML SGA AEZ1 LZZZ _ _ _1 _ _ _ _...
Page 82: ...www balluff com...
Page 107: ...espa ol Manual de instrucciones BML SGA AEZ1 LZZZ _ _ _1 _ _ _ _...
Page 108: ...www balluff com...
Page 133: ......