www.supportme.net
4-16 Input / Output
MN1929
4.5.3 Error output
The NextMove ST control card has an internal error output connected directly to the enable
inputs of the ST L297 stepper controllers (see section 4.3.1). The error output must therefore
be used to enable the axes. There are a number of methods for controlling the error output.
4.5.3.1 RELAY keyword
Because the NextMove ST control card is used in products that include a hardware relay, the
error output may be controlled directly by the
RELAY
keyword. The command
RELAY=1
will
enable the stepper controllers; the command
RELAY=0
will disable them.
4.5.3.2 DRIVEENABLEOUTPUT keyword
The
DRIVEENABLEOUTPUT
keyword can be used to configure the error output as the drive
enable output. For example, the command
DRIVEENABLEOUTPUT.1=_RELAY0
will mean
that the error output will be the drive enable output for axis 1. When axis 1 is enabled, the error
output will be activated and the axis enabled. If multiple axes are configured to use the error
output as their drive enable output, enabling one axis will enable all of them. Similarly, if one
axis is disabled, all will be disabled.
The
RELAY
keyword cannot control the error output if it is configured as a drive enable output.
4.5.3.3 GLOBALERROROUTPUT keyword
By default, the error output is used as the global error output. In the event of an error on any
axis, the global error output will be deactivated, disabling all axes. This action overrides the
state of the error output defined by other methods, such as the drive enable status or
RELAY
keyword. Alternatively, the
GLOBALERROROUTPUT
keyword can be used to configure a
general purpose digital output to be the global error output.
See the MintMT help file for details of each keyword.
4.5.3.4 Jumper settings
The operation of the error output is dependent on jumpers JP1, JP3, JP4 and JP5. Jumper
JP1 is situated next to the POWER IN connector on the baseboard, and must be set as shown
in Figure 18.
JP
1
JP
1
Normal operation
.
Stepper controller enable
inputs are under the control
of the NextMove ST Error
output.
Disable
.
Stepper controller outputs
are permanently disabled.
JP3 (do not fit)
JP4
JP5
JP1
Figure 18 - Error output jumper JP1
Jumpers JP3, JP4 and JP5 are situated at the edge of the NextMove ST control card, near the
end of the 50-pin expansion header. JP4 and JP5 must be fitted to allow correct operation of
the error output. The neighboring jumper JP3 must not be fitted.
Summary of Contents for NextMove ST
Page 1: ...NextMove ST Motion Controller MOTION CONTROL Installation Manual 1 04 MN1929...
Page 2: ......
Page 6: ...iv Contents MN1929...
Page 16: ...www supportme net 3 4 Basic Installation MN1929...
Page 62: ...www supportme net 6 8 Troubleshooting MN1929...
Page 70: ...Comments MN1929 Thank you for taking the time to help us...
Page 71: ......