Operation 6-21
MN1928
6.6.3 Overdamped response
If the graph shows that the response is overdamped (it reaches the demand too slowly, as
shown in Figure 50) then the value for KDERIV should be decreased to reduce the damping of
the move. If the overdamping is excessive, it may be necessary to increase the value of
KPROP.
Measured position
Demand
position
Figure 50 - Overdamped response
10. Click in the KDERIV and/or KPROP boxes
and make the required changes. The ideal