www.baldormotion.com
5-28 Backplanes
MN1928
5.3.7 Digital outputs 8-11 (NES002-501 / NES002-502 only)
Location
X5
Mating connector: Weidmüller Omnimate BL 3.5/5
Pin Name
Description
NextMove ES
96-pin
connector
5 DGND
Digital ground
a3
4 DOUT11
Digital output DOUT11
c22
3 DOUT10
Digital output DOUT10
c16
2 DOUT9
Digital output DOUT9
b13
1 DOUT8
Digital output DOUT8
a13
Digital outputs DOUT8 - DOUT11 on the backplane are
not
buffered by the
opto-isolator card; they are connected directly to the NextMove ES outputs.
When an output is activated, it is grounded through the ULN2003, which can sink up to 50 mA
per output (all outputs on, 100% duty cycle). If an output is used to drive a relay, a suitably
rated diode must be fitted across the relay coil, observing the correct polarity. This is to protect
the output from the back-EMF generated by the relay coil when it is de-energized.
DOUT8
NextMove ES
ULN2003
Mint
OUTX(8)
74AHCT244
DGND
GND
User
supply
24 V
User
supply
GND
Backplane
1
96
pin
connector
‘X5’
5
Output Load
(Relay with
flyback diode
shown)
Figure 39 - Digital output circuit (DOUT8-11) - DOUT8 shown
1
5
CAUTION
Servo Systems Co. • 115 Main Road • P.O. Box 97 • Montville, NJ,
07045-0097 • (973) 335-1007 • Toll Free: (800) 922-1103