A. AC Line Connection 

–  Wire  the

AC line input to L1 and L2 terminals
of Terminal Block TB1 as shown in
Figure 4.  Be sure 

both

Jumpers J1

and  J2  are  set  to  the  “115V”  posi-
tion for 115 Volt AC line input or to
the “230V” position for 208/230 Volt
AC line input.

B. Ground Connection 

Earth

ground  the  control  chassis  using
the green ground screw that is pro-
vided on the inside of the control to
the right side of Terminal Block TB1
as shown in Figure 4.

C. Motor Connection 

–  Wire  the

motor leads to U, V and W termi-
nals  of  Terminal  Block  TB1  as
shown  in  Figure  4.    Be  sure
Jumper J3 is set to the correspon-
ding motor horsepower rating.

D. Remote Main Speed

Potentiometer Connection 

The control is supplied with a
prewired Main Speed
Potentiometer mounted on the front cover.  To
operate the control from a remote potentiometer
(5kΩ), remove the white, orange, and violet
potentiometer leads from P1, P2 and P3 termi-
nals.  The leads may be taped and left inside the
control.  

The potentiometer assembly may be removed if a
watertight seal is used to cover the hole in the front
cover.    Connect  the  remote  main  speed  poten-
tiometer wires to P1 (low side), P2 (wiper) and P3
(high side) terminals as shown in Figure 5.

E. Remote Start/Stop Switch Connections 

–  The  control  is

supplied  with  a  prewired  Start/Stop  switch,  mounted  on  the
front cover.  To operate the control from a remote Start/Stop
Switch (type (ON)-OFF-ON, SPDT), remove the white, black
and  red  wires  from  RUN,  COM  and  STOP terminals.    The
leads  may  be  taped  and  left  in  the  control.    The  switch
assembly  may  be  removed  if  a  watertight  seal  is  used  to
cover  the  hole  in  the  front  cover.    Connect  the  remote
Start/Stop  Switch  wires  to  RUN  (momentary),  COM  (com-
mon)  and  STOP (constant)  terminals  as  shown  in  Figure  6.
After  applying  power,  momentarily  set  the  Start/Stop  Switch
to  the  "START"  position.    The  motor  will  operate  at  the  set  speed  of  the  Main  Speed
Potentiometer.  To stop the motor, set the Start/Stop Switch to the "STOP" position.

6

12

Supply Wire Gauge (AWG - Cu)

Minimum

Maximum

Designation

Connection

Maximum Tightening Torque

(in-lbs)

AC Line Input

Motor

L1, L2

U, V, W

22

12

22

12

12

TABLE 3 – TERMINAL BLOCK WIRING INFORMATION

TB1

L2 AC LINE

L1

W

V

U

MOTOR

AC LINE

MOTOR

(EARTH)

GROUND

FIGURE 4 – POWER CONNECTIONS

P2

P1

P3

CON1

(BACK VIEW)

ORANGE (WIPER)

WHITE (LOW)

VIOLET (HIGH)

MAIN SPEED POTENTIOMETER

FIGURE 5 – REMOTE MAIN SPEED

POTENTIOMETER CONNECTION

RED

WHITE

BLACK

START

STOP

START/STOP SWITCH

RUN

COM

STOP

R/F

FIGURE 6 – REMOTE START/STOP

SWITCH CONNECTION

RUN

COM

R/F

STOP

FIGURE 7 – START/STOP

FUNCTION ELIMINATED

(JUMPER INSTALLED)

Summary of Contents for ID5601-BO

Page 1: ...ADJUSTABLE SPEED DRIVE Series 5 Inverter NEMA 4X IP 65 8 01 MN781B Installation Operating Manual...

Page 2: ...ndication 12 Figures 1 Control Layout 3 2 Enlarged View of Trimpot Settings 3 3 Mechanical Specifications 4 4 Power Connections 6 5 Remote Main Speed Potentiometer Connection 6 6 Remote Start Stop Swi...

Page 3: ...ovided herein You must read the Safety Warning below before proceeding ii SAFETY WARNING Please read carefully This product should be installed and serviced by a qualified technician electrician or el...

Page 4: ...nual reset modes motor frequency frequency multiplier fixed or adjustable boost Optional accessories include a Forward Stop Reverse Switch Signal Isolator and Auto Manual Switch Quick connect terminal...

Page 5: ...P2 P1 P3 STOP FWD RUN REV COM STOP R F G B R Y POWER STATUS LED BOARD CON1 J1 115V 230V BC0 BC B B BC L2B L2A L1B L1A L2 AC LINE L1 W V U MOTOR TB1 1 2 1 4 3 4 1HP ADJ MULT 2X 1X FREQ 50HZ 60HZ BOOST...

Page 6: ...AUTO MANUAL STOP SPEED SHOWN WITH OPTIONAL AUTO MANUAL AND FORWARD STOP REVERSE RECOMMENDED MOUNTING SCREW 1 4 M6 2 53 139 97 5 51 128 59 5 06 7 97 0 31 5 86 9 53 224 00 8 82 208 17 8 20 241 96 64 35...

Page 7: ...nting and wiring close the cover making sure that the wires do not get caught or crimped as the cover is closed Tighten all four cover screws so that the gasket is slightly compressed Do not over tigh...

Page 8: ...own in Figure 5 E Remote Start Stop Switch Connections The control is supplied with a prewired Start Stop switch mounted on the front cover To operate the control from a remote Start Stop Switch type...

Page 9: ...pers Note Disconnect the AC line before changing position of jumpers A AC Line Voltage Selection J1 and J2 Jumpers J1 and J2 are both factory set to the 230V position for 208 230 Volt AC line input Fo...

Page 10: ...control to allow for AC line motor connections and any other wiring Although the control is designed for outdoor and wash down use care should be taken to avoid extreme hazardous locations where phys...

Page 11: ...itch is set to the ON position The STATUS LED will indicate control status as described in Section IX on page 13 To start the control momentarily set the Start Stop Switch to the START position The mo...

Page 12: ...nimum speed of the motor The MIN trimpot is factory set for 0 speed For a higher minimum speed setting rotate the MIN trimpot clock wise See Figure 18 C Acceleration ACCEL Sets the amount of time for...

Page 13: ...21 1 Wire an ammeter in series with one motor phase 2 Run the motor and set the unloaded speed to approxi mately 50 3 Load the motor to the rated motor nameplate current Amps AC 4 Adjust the COMP tri...

Page 14: ...0 RPM Note An unloaded motor with excessive boost will draw more current than a partial ly loaded motor 3 Adjust the BOOST trimpot until the ammeter reading reaches the motor nameplate rating 4 Using...

Page 15: ...connection diagrams are supplied with all accessories to facilitate installation A Forward Stop Reverse Switch ID5FSR 1 Provides motor reversing and stop func tions Mounts on the enclosure cover and i...

Page 16: ...damage including injury to any person caused by items of our manufacture or sale Some states do not allow the exclusion or limitation of inci dental or consequential damages so the above exclusion may...

Reviews: