background image

11

more rapid deceleration time, rotate the DECEL trimpot coun-
terclockwise.  For longer deceleration time, rotate the DECEL
trimpot clockwise.  See Figure 20.

Note:  

To  provide  increased  resolution  of  the  ACCEL and

DECEL trimpots, 50% rotation covers 0.3 - 5 seconds.

Application Note:

On  applications  with  high  inertial  loads,

the deceleration may automatically increase in time.  This will
slow down the rate of speed decrease to prevent the bus volt-
age from rising to the overvoltage trip point.  This function is
called regeneration protection.  

It is recommended that for

very high inertial loads that both the ACCEL and DECEL
trimpots should not be set to less than ten (10) seconds.

E. Slip Compensation (COMP) 

– Sets  the  amount  of

Volts/Hz/Amp  to  maintain  set  motor  speed  under  varying
loads.  The COMP trimpot is factory set for 1.5 Volts/Hz/Amp.
The slip compensation may be adjusted by the COMP trim-
pot as described below.  See Figure 21.

1. Wire an ammeter in series with one motor phase.

2. Run  the  motor  and  set  the  unloaded  speed  to  approxi-

mately 50%.

3. Load  the  motor  to  the  rated  motor  nameplate  current

(Amps AC).

4. Adjust the COMP trimpot so that the loaded RPM is equal

to the unloaded RPM.

5. The  motor  is  now  compensated  to  provide  constant

speed under varying loads.

F. Current Limit with I

2

t Shutdown (CL) 

– Sets  the  current

limit  (overload),  which  limits  the  maximum  current  to  the
motor.  The current limit set point is established by the setting
of Jumper J3 and the setting of the CL trimpot.  See Figure 22.

2.3

0.8

Shown Factory Set to 1.5 Volts/Hz/Amp

1.5

3

0

Volts/Hz/Amp

FIGURE 21

COMP TRIMPOT RANGE

(Shown Factory Set to 160%)

Percent of Range Setting

80

40

160

200

120

FIGURE 22

CL TRIMPOT RANGE

2.5

12.5

(Shown Factory Set to 1.5 Seconds)

1.5

5

Seconds

0.3

20

FIGURE 20

DECEL TRIMPOT RANGE

110

150

140

130

10

120

160

50

1.0

0.1

SETTING (160%)

FACTORY CL

FIGURE 23 – I

2

t TRIP TIME vs MOTOR CURRENT

NOTES:

1. The CL set point is factory set to 160% of nominal motor current.
2. I

2

t Will not trip below 120% of the CL setting.

MOTOR CURRENT (%)

I

2

t TRIP TIME

(minutes)

Summary of Contents for ID5601-BO

Page 1: ...ADJUSTABLE SPEED DRIVE Series 5 Inverter NEMA 4X IP 65 8 01 MN781B Installation Operating Manual...

Page 2: ...ndication 12 Figures 1 Control Layout 3 2 Enlarged View of Trimpot Settings 3 3 Mechanical Specifications 4 4 Power Connections 6 5 Remote Main Speed Potentiometer Connection 6 6 Remote Start Stop Swi...

Page 3: ...ovided herein You must read the Safety Warning below before proceeding ii SAFETY WARNING Please read carefully This product should be installed and serviced by a qualified technician electrician or el...

Page 4: ...nual reset modes motor frequency frequency multiplier fixed or adjustable boost Optional accessories include a Forward Stop Reverse Switch Signal Isolator and Auto Manual Switch Quick connect terminal...

Page 5: ...P2 P1 P3 STOP FWD RUN REV COM STOP R F G B R Y POWER STATUS LED BOARD CON1 J1 115V 230V BC0 BC B B BC L2B L2A L1B L1A L2 AC LINE L1 W V U MOTOR TB1 1 2 1 4 3 4 1HP ADJ MULT 2X 1X FREQ 50HZ 60HZ BOOST...

Page 6: ...AUTO MANUAL STOP SPEED SHOWN WITH OPTIONAL AUTO MANUAL AND FORWARD STOP REVERSE RECOMMENDED MOUNTING SCREW 1 4 M6 2 53 139 97 5 51 128 59 5 06 7 97 0 31 5 86 9 53 224 00 8 82 208 17 8 20 241 96 64 35...

Page 7: ...nting and wiring close the cover making sure that the wires do not get caught or crimped as the cover is closed Tighten all four cover screws so that the gasket is slightly compressed Do not over tigh...

Page 8: ...own in Figure 5 E Remote Start Stop Switch Connections The control is supplied with a prewired Start Stop switch mounted on the front cover To operate the control from a remote Start Stop Switch type...

Page 9: ...pers Note Disconnect the AC line before changing position of jumpers A AC Line Voltage Selection J1 and J2 Jumpers J1 and J2 are both factory set to the 230V position for 208 230 Volt AC line input Fo...

Page 10: ...control to allow for AC line motor connections and any other wiring Although the control is designed for outdoor and wash down use care should be taken to avoid extreme hazardous locations where phys...

Page 11: ...itch is set to the ON position The STATUS LED will indicate control status as described in Section IX on page 13 To start the control momentarily set the Start Stop Switch to the START position The mo...

Page 12: ...nimum speed of the motor The MIN trimpot is factory set for 0 speed For a higher minimum speed setting rotate the MIN trimpot clock wise See Figure 18 C Acceleration ACCEL Sets the amount of time for...

Page 13: ...21 1 Wire an ammeter in series with one motor phase 2 Run the motor and set the unloaded speed to approxi mately 50 3 Load the motor to the rated motor nameplate current Amps AC 4 Adjust the COMP tri...

Page 14: ...0 RPM Note An unloaded motor with excessive boost will draw more current than a partial ly loaded motor 3 Adjust the BOOST trimpot until the ammeter reading reaches the motor nameplate rating 4 Using...

Page 15: ...connection diagrams are supplied with all accessories to facilitate installation A Forward Stop Reverse Switch ID5FSR 1 Provides motor reversing and stop func tions Mounts on the enclosure cover and i...

Page 16: ...damage including injury to any person caused by items of our manufacture or sale Some states do not allow the exclusion or limitation of inci dental or consequential damages so the above exclusion may...

Reviews: