WARNING!  The motor will automatically start when the AC line is applied or a
fault is cleared, if Jumper J4 is set to the “AUTO” or “MAN” position and the

Start/Stop Switch is eliminated.

VII. AC LINE FUSING

This  control  does  not  contain  AC  line  fuses.    Most  electrical  codes  require  that  each
ungrounded conductor contain circuit protection.  It is recommended to install a 20 Amp fuse
(Littelfuse 326, Buss ABC or equivalent) or a circuit breaker in series with each ungrounded
conductor.  Check all electrical codes that apply to the application.  

Do not fuse motor leads.

VIII. TRIMPOT ADJUSTMENTS

The control circuit board contains trimpots, which are factory set
for most applications.  Figure 2, on page 3 illustrates the location
of the trimpots and their approximate factory calibrated positions.
Some  applications  may  require  readjustment  of  the  trimpots  in
order  to  tailor  the  control  for  a  specific  requirement.    Readjust
trimpots as described below.

WARNING!  If possible, do not adjust trimpots with
the main power applied.  If adjustments are made

with the main power applied, an insulated adjustment tool
must be used and safety glasses must be worn.  High volt-
age exists in this control.  Fire and/or electrocution can
result if caution is not exercised.  Safety Warning, on page 1,
must be read before proceeding.

A. Maximum Speed (MAX):

Sets  the  maximum  speed  of  the

motor.  The MAX trimpot is factory set for 100% of base motor
speed.  For a higher maximum speed setting, rotate the MAX
trimpot  clockwise.    For  a  lower  maximum  speed  setting,
rotate the MAX trimpot counterclockwise.  See Figure 17.

B. Minimum Speed (MIN):

Sets  the  minimum  speed  of  the

motor.   The  MIN  trimpot  is  factory  set  for  0%  speed.    For  a
higher minimum speed setting, rotate the MIN trimpot clock-
wise.  See Figure 18.

C. Acceleration (ACCEL):

Sets  the  amount  of  time  for  the

motor  to  accelerate  from  zero  speed  to  max  speed.    The
ACCEL trimpot  is  factory  set  for  1.5  seconds  acceleration.
For  more  rapid  acceleration  time,  rotate  the ACCEL trimpot
counterclockwise.    For  longer  acceleration  time,  rotate  the
ACCEL trimpot clockwise.  See Figure 19.

Note:  

Rapid acceleration settings may cause the current limit

circuit to activate, which will extend the acceleration time.

D. Deceleration (DECEL):

Sets the amount of time for the motor to decelerate from max

speed to zero speed.  The DECEL trimpot is factory set for 1.5 seconds deceleration.  For

!

90

75

(Shown Factory Set to 100%)

100

80

Percent of Frequency Setting

70

110

FIGURE 17

MAX TRIMPOT RANGE

35

15

(Shown Factory Set to 0%)

40

30

0

Percent of Frequency Setting

FIGURE 18

MIN TRIMPOT RANGE

Disconnect and reconnect the AC
line.

Fault

Auto Mode

with Start/Stop Switch Installed

Manual Mode

with Start/Stop Switch Installed

Auto or Manual Mode

with Start/stop Switch Removed

Undervoltage

Overvoltage

Short Circuit

I

2

t

Control will automatically reset.

Reset the control with the
Start/Stop Switch.

Control will automatically reset.

Control will automatically reset.

Control will automatically reset.

Reset the control with the
Start/Stop Switch.

Reset the control with the
Start/Stop Switch.

Reset the control with the
Start/Stop Switch.

Reset the control with the
Start/Stop Switch.

Control will automatically reset.

Control will automatically reset.

TABLE 4 – FAULT RECOVERY & RESETTING THE CONTROL*

*Fault must be cleared before the control can be reset.

!

2.5

12.5

(Shown Factory Set to 1.5 Seconds)

1.5

5

Seconds

0.3

20

FIGURE 19

ACCEL TRIMPOT RANGE

Summary of Contents for ID5601-BO

Page 1: ...ADJUSTABLE SPEED DRIVE Series 5 Inverter NEMA 4X IP 65 8 01 MN781B Installation Operating Manual...

Page 2: ...ndication 12 Figures 1 Control Layout 3 2 Enlarged View of Trimpot Settings 3 3 Mechanical Specifications 4 4 Power Connections 6 5 Remote Main Speed Potentiometer Connection 6 6 Remote Start Stop Swi...

Page 3: ...ovided herein You must read the Safety Warning below before proceeding ii SAFETY WARNING Please read carefully This product should be installed and serviced by a qualified technician electrician or el...

Page 4: ...nual reset modes motor frequency frequency multiplier fixed or adjustable boost Optional accessories include a Forward Stop Reverse Switch Signal Isolator and Auto Manual Switch Quick connect terminal...

Page 5: ...P2 P1 P3 STOP FWD RUN REV COM STOP R F G B R Y POWER STATUS LED BOARD CON1 J1 115V 230V BC0 BC B B BC L2B L2A L1B L1A L2 AC LINE L1 W V U MOTOR TB1 1 2 1 4 3 4 1HP ADJ MULT 2X 1X FREQ 50HZ 60HZ BOOST...

Page 6: ...AUTO MANUAL STOP SPEED SHOWN WITH OPTIONAL AUTO MANUAL AND FORWARD STOP REVERSE RECOMMENDED MOUNTING SCREW 1 4 M6 2 53 139 97 5 51 128 59 5 06 7 97 0 31 5 86 9 53 224 00 8 82 208 17 8 20 241 96 64 35...

Page 7: ...nting and wiring close the cover making sure that the wires do not get caught or crimped as the cover is closed Tighten all four cover screws so that the gasket is slightly compressed Do not over tigh...

Page 8: ...own in Figure 5 E Remote Start Stop Switch Connections The control is supplied with a prewired Start Stop switch mounted on the front cover To operate the control from a remote Start Stop Switch type...

Page 9: ...pers Note Disconnect the AC line before changing position of jumpers A AC Line Voltage Selection J1 and J2 Jumpers J1 and J2 are both factory set to the 230V position for 208 230 Volt AC line input Fo...

Page 10: ...control to allow for AC line motor connections and any other wiring Although the control is designed for outdoor and wash down use care should be taken to avoid extreme hazardous locations where phys...

Page 11: ...itch is set to the ON position The STATUS LED will indicate control status as described in Section IX on page 13 To start the control momentarily set the Start Stop Switch to the START position The mo...

Page 12: ...nimum speed of the motor The MIN trimpot is factory set for 0 speed For a higher minimum speed setting rotate the MIN trimpot clock wise See Figure 18 C Acceleration ACCEL Sets the amount of time for...

Page 13: ...21 1 Wire an ammeter in series with one motor phase 2 Run the motor and set the unloaded speed to approxi mately 50 3 Load the motor to the rated motor nameplate current Amps AC 4 Adjust the COMP tri...

Page 14: ...0 RPM Note An unloaded motor with excessive boost will draw more current than a partial ly loaded motor 3 Adjust the BOOST trimpot until the ammeter reading reaches the motor nameplate rating 4 Using...

Page 15: ...connection diagrams are supplied with all accessories to facilitate installation A Forward Stop Reverse Switch ID5FSR 1 Provides motor reversing and stop func tions Mounts on the enclosure cover and i...

Page 16: ...damage including injury to any person caused by items of our manufacture or sale Some states do not allow the exclusion or limitation of inci dental or consequential damages so the above exclusion may...

Reviews: