(IEC)
IECEx FMG 07.0007X
{Certificate Number}
Ex ia IIC T6..T4 Ga
{Intrinsically Safe}
Ex db mb IIC T6..T4 Gb;
{Explosion proof, gas}
Ex tb IIIC T96°C Db
{Protection by enclosure, dust}
Ta=-40°C
to
+85°C
{Operating
Temperature}
IP66
{Ingress
Protection}
6.3
Operating Ranges
6.3.1 Temp:
-40°C
to
+85°C
6.3.2
Voltage: 30 Volts
6.3.3 Pressure:
150
psig
(1.03MPa)
6.3.4 Current:
4-20mA
6.4
Enclosure Type
Type 4X-IP66
6.5
Temperature Code
T6 Ta=60°C, T5 Ta=75°C, T4 Ta=85°C
6.6
Notes Related to Explosionproof Rating
DO NOT OPEN EVEN WHEN ISOLATED WHEN EXPLOSIVE ATMOSPHERES
ARE PRESENT
6.7
Notes Related to Intrinsic Safety
1) REFER TO ES-699 FOR ADDITIONAL CAUTIONS OR WARNINGS
2) Supply Connection Wiring Rated for 5ºC above Max Ambient
3) PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE
HAS BEEN MARKED, IT CAN NOT BE CHANGED
6.8
Model Code:
SVI2-abcdefgh
(see section 3 above for explanation)
6.9
Serial Number:
SN-nnyywwnnnn