Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
| 109
© 2020 Baker Hughes Company. All rights reserved
.
General Configuration Notes
The SVI II AP supports two identical contact outputs, SW #1
and SW #2 (Digital Output switches), that can be logically
linked to status bits.
The switches are polarity sensitive and must be connected only
to a DC circuit. The switch (+) terminal must be electrically
positive with respect to the (–) terminal. If the (+) terminal is
electrically negative with respect to the (–) terminal, then the
switch will conduct, regardless of switch state.
If the switch is connected directly across the power
source, the current will be limited only by the capacity of
the power source and the switch can be damaged.
This section discusses the necessary precautions when
configuring a system.
Without a load, when the switch is on (closed) the external
voltage would be dropped across the switch.
This damages
the switch
34).
Figure 34
Switch Installation Drawing without Load: Configuration
Not Allowed
SVI II AP
Switch
Output
External
Voltage
Source
NOT ALLOWED
Full voltage
drop is
occurring
across the
switch (no
current limit in
place)
+
-
-
+
B: Optional Switch
Load Limits