Configuration Menu
Because calibration depends on certain configuration options
you must perform Configuration before you perform Calibration
when installing the SVI II AP for the first time.
If a change is made in the Air-to-Open / Air-to-Close
configuration option or if you move the SVI II AP to a different
valve or make any change to the valve position linkage, you
must run the find STOPS calibration again.
Figure 28
CONFIGure Menu