Configuration with Pushbuttons
Prior to changing the SVI II AP configuration, check the
existing configuration.
Viewing Configuration Data
To view SVI II AP configuration data:
1. Access the VIEW DATA menu from the MANUAL menu by
pressing the
+
button.
2. In the VIEW DATA menu, press
*
to examine the
configuration.
3. Press
+
to scroll through and observe the factory
configuration.
4. Press
+
until MANPOS appears.
5. Select with
*
.
6. When the adjustment screen appears stroke the valve
open by h down. The rate of set point change is
slow to begin, but increases speed while the + is pressed.
7. Stroke the valve to several values.
8. Verify the action is as desired.
9. Press
+
to move to the
SETUP
menu.
10. In the
SETUP
menu press the
*
button to access the
CONFIGuration
menu.
11. In the
CONFIG
menu set the configuration parameters.
12. When in
CONFIGure
or
CALIBrate
, pressing
*
changes
values.
13. Return to
NORMAL
mode. The valve moves to the value
set by the current calibrator.
14. Stroke the valve through its range to verify that the
movement is as desired.