Auto Tune
This process takes 3 to 10 minutes and strokes the valve in
large and small steps to set the PID parameters for best
positioning response.
WARNING
DO NOT perform STOPS while the valve is controlling
the process.
DO NOT perform Auto Tune while the valve is con-
trolling the process.
To auto tune the SVI II AP:
1. Press
*
to begin the autoTUNE procedure.
As autoTUNE proceeds, numerical messages display,
indicating the procedure is working.
2. When autoTUNE is complete,
TUNE
appears.
3. Press
+
repeatedly until
SETUP
appears.
4. Press
* t
o return to SETUP menu;
CALIB
appears.