INSTALLATION
IMHSS03 MODULE INSTALLATION
3 - 10
I-E96-322A
®
IMHSS03 MODULE INSTALLATION
To install the HSS module in the module mounting unit:
1. Locate the module mounting unit slot assignment for the
module.
2. Check the I/O expander bus dipshunt socket on the back-
plane of the module mounting unit. The dipshunt must be
installed with all pins shorted. There must be a communica-
tion path from the MFP module to the I/O module.
3. Align the top and bottom edges of the circuit card with the
top and bottom rails of the assigned slot in the module mount-
ing unit.
4. Slide the module into the slot. Push until the module is
seated in the backplane connector. Turn the 2 thumbscrews
on the faceplate ½-turn until the module locks in place.
Figure 3-2. IMHSS03 Jumper Layout
J25
J24
J23
J22
J21
J20
J19
J9
J8
J18
J17
J16
J15
J14
J13
J12
J11
J10
J7
J27 J29
J3
J5
J6
J1
J4
J26
J28
J30
J2
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
4
1
4
1
4
1
4
1
4
1
4
1
4
1
4
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
TP25461A
WARNING
Disconnect power before installing dipshunts on the module
mounting unit backplane. Failure to do so will result in contact
with cabinet areas that could cause severe or fatal shock.
AVERTISSEMENT
Interrompez l'alimentation avate d'installer des dipshunts sur
le fond de panier du châssis de montage des modules. Sinon,
tout contact avec cette zone entraîne des risques d'électrocu-
tion sérieuse ou fatale.