INSTALLATION
JUMPER SETTINGS
I-E96-322A
3 - 9
20 - 160 mA I/H converter
1-2
J8
2-3
J9-J13, J18-J21
3-4
J14-J17, J22-J25
4 - 20 mA I/H converter
1-2
J9
2-3
J8, J10-J13, J18-J21
3-4
J14-J17, J22-J25
±8 mA servo outputs
1-2
J10, J18
2-3
J8, J9, J11-J14, J19-J22
3-4
J15-J17, J23-J25
±16 mA servo outputs
1-2
J10, J11, J18, J19
2-3
J8, J9, J12-J15, J20-J23
3-4
J16, J17, J24, J25
±24 mA servo outputs
1-2
J10-J12, J18-20
2-3
J8, J9, J13-J16, J21-J24
3-4
J17, J25
±32 mA servo outputs
1-2
J10-J13, J18-J21
2-3
J8, J9, J14-J17, J22-J25
±40 mA servo outputs (servo1/C1
and servo2/C1 outputs only)
1-2
J10-J14, J18-J22
2-3
J8, J9
3-4
J15-J17, J23-J25
±48 mA servo outputs (servo1/C1
and servo2/C1 outputs only)
1-2
J10-J15, J18-J23
2-3
J8, J9
3-4
J16, J17, J24, J25
±56 mA servo outputs (servo1/C1
and servo2/C1 outputs only)
1-2
J10-J16, J18-J24
2-3
J8, J9
3-4
J17, J25
±64 mA servo outputs (servo1/C1
and servo2/C1 outputs only)
1-2
J10-J25
2-3
J8, J9
AC LVDT (sine wave output to
primary)
1-2
J27-J30
DC LVDT (15 VDC output for
LVDT power)
2-3
Normal operation
1-2
J31
Microcontroller clock disabled
(internal test only)
open
NOTE: To enable a function, place jumper straps over (short) the required jumper positions.
Table 3-6. Jumpers J1 through J31
(continued)
Function
Jumper
Position
Jumper