INSTALLATION
INSTALLING THE TERMINATION UNIT OR MODULE
I-E96-322A
3 - 3
NTHS03 Termination Unit Installation
Use the NTHS03 termination unit to operate the HSS module
with full IMHSS03 functionality. This termination unit can also
terminate an IMHSS03 module configured for IMHSS02 func-
tionality. To install the NTHS03 termination unit:
1. Refer to the THS termination unit product instruction or
to select the required dipshunt and jumper
settings.
2. Follow the steps in the THS product instruction to mount
the termination unit to the field termination panel.
3. Connect the wiring from the servo valve or I/H converter,
linear variable differential transformer, and digital I/O to the
termination unit.
4. Follow the steps in the THS product instruction to connect
the NKHS03 cable to the module mounting unit (MMU) slot for
the HSS module and to the termination unit.
5. Follow the procedures in the termination unit product
instruction to connect I/O common and 24 VDC on the system
power bus bar to the termination unit.
NIDI01 Termination Module Installation
Two NIDI01 termination modules are required to terminate an
HSS module with IMHSS03 functionality. To terminate an HSS
module with IMHSS02 functionality, only one termination
module is required. To install the NIDI01 termination module:
1. Refer to the IDI termination module product instruction or
to select the required jumper settings.
2. Follow the steps in the IDI product instruction to mount
the termination module to the field termination panel.
3. Connect wiring from the servo valve or I/H converter, linear
variable differential transformer, digital I/O, 24 VDC and I/O
common to the termination module.
4. Follow the steps in the IDI product instruction to connect
the NKAS02 cable to the MMU slot for the HSS module and to
the termination module.