INTRODUCTION
I-E96-303A
B - 1
APPENDIX B - TERMINATION MODULE (NIDI01)
CONFIGURATION
INTRODUCTION
The IMASO01 uses an NIDI01 for termination. Jumpers on the
Termination Module (NIDI01) configure the analog outputs
that are sent to the process. The Analog Slave Output (ASO)
module outputs are 1 to 5 VDC or 4 to 20 mA depending on the
ASO module configuration.
Figures
B-1
and
B-2
show the NIDI01, and the analog signal
path from the ASO module to the field device for a termination
module application. These figures show an application using
an IMASO01, NIDI01 and an external load. Refer to Table
B-1
to determine the jumper setting to configure your application.
Figure
B-3
shows the terminal assignments for the analog out-
put signals. Refer to this figure when connecting field wiring to
the NIDI01.
Figure B-1. NIDI01 Circuit Diagram (Voltage Mode)
TP27158A
IMASO01
(REPRESENTATIVE
CIRCUIT)
NKTU01
NIDI01
FIELD
WIRING
FIELD
DEVICE
+24 VDC
P3
P1
+
–
LOAD
TERMINALS
4-17, 19-32
FEEDBACK
+
–