![Bailey INFI 90 IMASO01 Instruction Download Page 29](http://html.mh-extra.com/html/bailey/infi-90-imaso01/infi-90-imaso01_instruction_467116029.webp)
OPERATING PROCEDURES
START-UP PROCEDURES
4 - 2
I-E96-303A
®
START-UP PROCEDURES
The Multi-Function Processor (MFP) controls the start-up of
the ASO module; it is fully automatic. Function Code (FC) 149
in the MFP configuration enables the ASO. Specification 1 (FC
149) is the slave module address. It must be the same as the
address set on the address dipswitch (S1). The front panel LED
(solid green) verifies that the module is enabled and communi-
cating.
Table 4-1. IMASO01 Status LED Indicator
LED
Indication
Solid Green
Enabled and communicating with master module
Off
No power or not enabled
Solid Red
Bus fault timer error (
time out)