DESCRIPTION AND OPERATION
LOGIC POWER
2 - 6
I-E96-303A
®
LOGIC POWER
Logic power (+5 VDC and
±
15 VDC) drives the ASO circuits. It
connects through the top 12-pin card edge connector (P1)
shown in Figure
2-1
. P3 su24 VDC to operate the ana-
log output circuits.
BUS FAULT TIMER
The bus fault timer is a one-shot timer that is reset by the slave
expander bus clock; the master module generates the bus
clock. If the clock stops (indicating a master module error or
failure), the bus fault timer times out in 10 milliseconds. This
causes the analog outputs to change to their default values.
The front panel status LED turns red to indicate a bus fault
(
time-out
).
STATUS LED INDICATOR
A front panel module status LED indicator shows the operating
state of the ASO. Circuits on the ASO determine the module
status and light the LED accordingly. It lights green to indicate
normal operation.
Section 4
explains the indications and
Section 5
explains corrective actions to take.