TROUBLESHOOTING
ERROR INDICATIONS AND CORRECTIVE ACTION
5 - 2
I-E96-303A
®
The address set on address switch (S1) and in the MFP config-
uration must be the same. The MFP generates a MISSING
SLAVE MODULE error if they do not match. Verify that the
address set on S1 is the same as the address in FC 149 specifi-
cation 1. If not:
1. Remove the module and change the setting of S1 to corre-
spond with the MFP configuration (refer to
Section 3
for the
procedures to set an address and to install a slave module).
OR
2. Modify the address in the MFP configuration (FC 149 speci-
fication 1) to correspond with the address set on S1. Use an Infi
90 operator interface to modify the configuration (for proce-
dures on how to modify a function code specification, refer to
the Product Instruction for the operator interface you are
using).
Table 5-1. Status LED Indications and Corrective Actions
LED State
Indication
Probable Cause
Corrective Action
Solid Green
Slave module operating
normally and communi-
cating with master mod-
ule
Normal operation
No action required
Off
Slave module not
enabled
Address set on S1 not the
same as address in master
module configuration FC 149
spec 1
Change address on S1 to corre-
spond with FC 149 spec 1
OR
Change address in FC 149 spec
1 to correspond with S1
Dipshunt not properly installed
between master module and
slave module
Verify dipshunt is installed prop-
erly (no bent pins) in slave
expander bus socket on MMU
backplane between master and
slave module
Master module configuration
is not correct
Verify FC 149 is in master mod-
ule configuration
No power to slave mod-
ule
Module not completely
inserted in MMU
Verify module is completely
inserted in MMU: faceplate flush
with MMU and captive retaining
screws latched
Red
Bus fault timer error
(
time-out)
Slave expander bus clock fail-
ure
Check master module for proper
operation
Dipshunt not installed
between master and slave
module
Verify dipshunt is installed in the
slave expander bus socket on the
MMU backplane between master
and slave module