![Bailey INFI 90 IMASO01 Instruction Download Page 15](http://html.mh-extra.com/html/bailey/infi-90-imaso01/infi-90-imaso01_instruction_467116015.webp)
INTRODUCTION
SPECIFICATIONS
I-E96-303A
1 - 5
SPECIFICATIONS
REFERENCE DOCUMENTS
Power Requirements
Voltage
Current Consumption
Power Dissipation
+5 VDC
±
5%
+15 VDC
±
5%
-15 VDC
±
5%
+24 VDC
±
10% (from termination unit/termination module)
480 mA (+5 VDC)
200 mA (+15 VDC)
195 mA (-15 VDC)
310 mA (+24 VDC)
3.75 watts @ +5 VDC
5.25 watts @ +15 VDC
3.75 watts @ -15 VDC
D/A Resolution
10 bits for analog outputs
Output Accuracy
≤
0.15% (voltage mode)
≤
0.25% (current mode)
Output Load
750 ohms maximum (current mode)
22 kilohms minimum (voltage mode)
Current Limiting
Short Circuit Protection
50 mA (nominal) output current limit
Surge Protection
Meets IEEE-472-1974 Surge Withstand Capability Test
1
Mounting
Occupies one slot in standard INFI 90 Module Mounting Unit.
Environmental
Ambient Temperature
Relative Humidity
Altitude
Air Quality
0
o
to 70
o
C (32
o
to 158
o
F)
0% to 95% up to 55
o
C (131
o
F)(non-condensing)
0% to 45% at 70
o
C (158
o
F)(non-condensing)
Sea Level to 3 Km (1.86 miles)
Non-corrosive
Certification
CSA certified for use as process control equipment in an ordinary
(non-hazardous) location.
NOTE: 1. Do not use the NKTM01 cable when compliance with IEEE-472-1974 is necessary.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
Document
Number
Description
I-E92-501-2
Configuration and Tuning Terminal
I-E93-916
Engineering Work Station
I-E96-100
Operator Interface Station
I-E96-200
Function Code Application Manual
I-E96-201
Multi-Function Processor (IMMFP01)
I-E96-202
Multi-Function Processor (IMMFP02)
I-E96-410
Digital I/O Termination Module (NIDI01)
I-E96-424
Digital I/O Termination Module (NTDI01)
I-E96-303A1
31 March 1993