TROUBLESHOOTING
GENERAL FAILURES
5 - 6
I-E96-117B
®
Figure 5-2. Error Codes E03, E04, E05 and E06
Troubleshooting Flowchart
Y ES
N O
MEASURE ANALOG
INPUT VOLTAGE AT
TERMINATION UNIT
IS
VOLTAGE WITHIN
SPEC?
REPLACE
STATION
YE S
N O
YE S
N O
YE S
NO
DONE
REPLACE
TU/TM
REPLACE
STATION CABLE
IS
VOLTAGE WITHIN
SPEC?
YE S
N O
CONTACT
BAILEY
CONTROLS
VERIFY AI
DIPSHUNT
SETTING
VERIFY CORRECT
OPERATION OF
FIELD DEVICE AND
FIELD WIRING
MEASURE
VOLTAGE AT TU
ERROR CODE E03, E04, E05
OR E06 ON ALPHANUMERIC DISPLAY
ERROR CODE
REMAINS?
ERROR CODE
REMAINS?
ERROR CODE
REMAINS?
T00 306A