INTRODUCTION
SPECIFICATIONS
1 - 8
I-E96-117B
®
SPECIFICATIONS
lists the specifications of the SAC station.
NKDS13
DCS cable with connector non-PVC
NKSE01
Station serial extension cable
NKSE02
Station serial extension cable non-PVC
NKTD01/02
Termination station cable
NKTD11 /12
Termination station cable non-PVC
NKTU01
Termination unit cable
NKTU11
Termination unit cable non-PVC
NTCS04
Control I/O termination unit
NTRL03
Remote link termination unit
Table 1-3. Nomenclature
(continued)
Nomenclature
Hardware
Table 1-4. IISAC01 Analog Control Station Specifications
Property
Characteristic/Value
Displays
3 gas plasma bar graphs (200 segments for process variable and set
point at 0.5% resolution, 100 segments for output at 1.0% resolution)
8-character, 14-segment, alphanumeric display
Bypass
Automatic entry or selected from faceplate
Communication
5 or 40 kbaud RS-485 serial link to the controlling module through the
termination unit
40 kbaud with any IMMFP03 module or IMMFP01 and IMMFP02 mod-
ule with firmware revision level C_0 or higher
All other modules are 5 kbaud
Size
72 mm x 144 mm x 381 mm (2.82 in. x 5.67 in. x 15.0 in.)
Mounting
Flush panel mounting
Supply voltage
(at the termination device)
21.6 VDC minimum, 27.0 VDC maximum
Power consumption
(at the termination device)
540 mA at 24 VDC
Analog output:
Current
Maximum load (compliance)
Accuracy
D/A resolution
Maximum load inductance
3 to 21 mA
600
Ω
maximum
2.0% of span at 25°C (77°F)
8 bits
600 mH