INTRODUCTION
WBPEEUI220760A0
4 - 1
SECTION 4 - TROUBLESHOOTING
INTRODUCTION
This section provides some very basic troubleshooting guide-
lines for the OIS43 console. It is not meant to be all inclusive.
Make certain all the manufacturer’s documentation on non
Elsag-Bailey OIS43 components is accessible. Three other
instruction manuals (Elsag-Bailey) should be on hand;
Opera-
tion
,
Configuration
and
File Utilities
. Those instruction
numbers are listed in Table
. Many of these documents pro-
vide troubleshooting information. If problems exist which are
not covered in any of the provided documentation, contact
Elsag-Bailey technical services personnel for assistance.
This section contains a general troubleshooting table, diagnos-
tic AC/DC power test procedures, module failure LED codes
and techniques for gathering information on software faults.
Close and secure cabinet doors after troubleshooting and
before returning the system to normal operation.
NOTE: Put circuit boards containing MOS devices into antistatic
bags when stored or shipped back to the factory.
Do not repair
printed circuit boards in the field. All repairs and adjustments should
be performed by qualified personnel.
TROUBLESHOOTING
The general troubleshooting guide in Table
may help to
identify problems and suggest solutions.
WARNING
There are exposed AC and DC connections inside the cabinet.
These exposed electrical connections present a shock hazard
that can cause injury or death.
AVERTISSEMENT
Cette armoire comporte des connexions c.a. et c.c. dénudées.
Ces connexions électriques présentent un danger d'électrocu-
tion pouvant entraîner des blessures ou la mort.
Table 4-1. Troubleshooting Guide
Symptom
Possible Problem or Solution
No power indicator on
circuit
No AC power at console. Check AC wiring on input. Check AC on power entry
panel. Check breaker light on power entry panel. Check fuse on power supply.
Breaker off but indicator on
Check breaker contacts. Check breaker wiring. Check AC input wiring.
Improper/ incomplete
start-up
Refer to diagnostic message at start-up for possible problems. Refer to the
CPU