Advanced
Encoder Protocol
Protocol Type
The Protocol Type enables the encoder interface . Selecting V1 or V2
automatically configures the Digital Input and Digital Output #1 for
encoder operation . Manually configuring the input and output for encoder
operation is not allowed and results in an error .
See
“Encoder Protocol Interface” on page 57
for further details .
V1 – Standard encoder protocol
V2 – Enhanced encoder protocol, provides additional digital information
Disabled – disables and removes encoder configuration
Totalizer Dials
Set the totalizer dial to 4…10 to select the number of digits for the totalizer to display . For example,
setting the dial to 6 causes the totalizer to display six digits (12 .3456 USG)
OTE:
N
A totalizer roll over can be indicated by a totalizer alarm via the digital output .
Totalizer
Resolution
[Off]
U
Use Totalizer Resolution to establish the number of units of measure that have to accumulate before
the display totalizers are updated . This is also known as setting the number of “dead” zeroes in the
display totalizer . For example:
Totalizer Resolution less than 1
Totalizer
Resolution
Example
OFF
0 .00000 USG
0 .00012 USG
0 .00123 USG
0 .01234 USG
0 .12345 USG
0 .0001
0 .0000 USG
0 .0001 USG
0 .0012 USG
0 .0123 USG
0 .1234 USG
0 .001
0 .000 USG
0 .000 USG
0 .001 USG
0 .012 USG
0 .123 USG
0 .01
0 .00 USG
0 .00 USG
0 .00 USG
0 .01 USG
0 .12 USG
0 .1
0 .0 USG
0 .0 USG
0 .0 USG
0 .0 USG
0 .1 USG
Totalizer Resolution greater than or equal to 1
Totalizer
Resolution
Example
OFF
0 .00000 USG
1 .23456 USG
12 .34567 USG 123 .4567 USG 1234 .456 USG
1
0 USG
1 USG
12 USG
123 USG
1234 USG
10
0 USG
0 USG
10 USG
120 USG
1230 USG
100
0 USG
0 USG
0 USG
100 USG
1200 USG
1000
0 USG
0 USG
0 USG
0 USG
1000 USG
To change the Totalizer Resolution, follow these steps from the
Advanced
menu:
1 . Select
Totalizer Resolution
to view the
Totalizer Resolution
display .
2 . Select a resolution .
3 . Press
[
E
] to save the option and to return to the
Advanced
menu .
Backlight Control
[Timed Off]
U
Use Backlight Control to set the backlight to: Always On, Always Off or Timed Off .
When set to Timed Off, the backlight automatically turns off after one minute of inactivity (no buttons
pressed) . Pressing any button turns the backlight on, but does not immediately navigate the menu .
To change Backlight Control, follow these steps from the
Advanced
menu:
1 . Select
Backlight Control
to view the
Backlight Control
display .
2 . Select an option .
3 . Press
[
E
] to save the option and to return to the
Advanced
menu .
Longer operation with the backlight set to “Always On” can reduce LCD lifespan .
Using the Main Menu Programming Options
Page 49
March 2022
MAG-UM-01272-EN-21