Tan Delta
© b2 electronic GmbH
DHV0086 Rev06
83
Step
Procedure
(Manual TD test)
TD4: Start Test
Start the test when the test parameters
displayed on the “Manual Test” screen are
correct. Rotate the navigation knob until the
“Start” field is highlighted. To run the test,
push in the knob.
TD5: HV Activation
Once the activation screen appears, press
the HV switch
40
within 10 seconds.
If the HV switch is not activated within 10
seconds, the “Manual Mode” screen will
reappear.
TD6: Test Startup
Startup appears on the screen to indicate
that the HVA is initializing the test.
TD7: Set Test Voltage
(if not pre-set in step MS 8)
Rotate the navigation knob
41
to modify
the voltage value.