Tan Delta
© b2 electronic GmbH
DHV0086 Rev06
80
6�2�2�1 Option with corona shield
Far End
Far End
Option with corona
Option with corona and guard on far end
Near End
Near End
23
23
17
24
25
26
17
K1
K1
K3
K3
K4
K2
NOTICE
For voltages from 15 kV we recommend the use of corona shields for TD
diagnostics.
Follow the introduction VLF withstand test with Tan Delta and guard
see
6.2.2 Connection Diagram: VLF withstand test with Tan Delta and guard on
page 78.
And replace S4 with OS1 to OS5 and continue with S5�
Step
Procedure
Art� Nr�
Connections on near end:
OS1
Mount corona shield to the DUT.
• Mount the corona shield at the phase to be tested
K1
.
KMD0081
OS2
Fix the hook and loop fastener.
• Fix the hook an loop fastener at the termination
23
.
KMSO0064
OS3
Connect the guard connection cable:
• Connect the cable at the 4 mm socket jack at the HV test lead
17
.
• Connect the other end of the cable at the conducting hook and loop fastener
23
.
KEK0126
Connections on far end:
OS4
Mount corona shield to the DUT.
• Mount corona shield on the same phase
K3
at the far end.
KMD0081