• When there is a G.SOAK wait at the start of a segment and the ON Time is set
to 0, the output goes on at start of the G.SOAK wait and the On Time starts as
the G.SOAK wait ends.
The output time = G.SOAK time + (Off Time – On Time) (See segment 10 in
the figure.)
• An On Time and Off Time occurring at the end of a RAMP-X segment are valid
when there is a G.SOAK wait at the end of a segment or as the end state of the
final segment. (See segment 10 in the figure.)
Note, however, that an On Time or Off Time setting at the end of a RAMP-T
segment is either valid or invalid depending on the computational error.
On-time
Off-time
Output-ON
Output-OFF
8
G.SOAK wait
Start of segment 8
The output goes on at the start of
segment 8 when on is set to 0.
Segment
Chapter 5. FUNCTIONS
On-time
Off-time
Output-ON
Output-OFF
9
ON = Segment time
10
Segment time
G.SOAK wait
ON = Segment time
Segment
On-time
Off-time
Output-ON
Output-OFF
Segment