7-13
■
Settings by event type
For information on event operations, see “
■
Events
”
(pages 5-5 to 5-15)
.
Event type
0
2
3
1
Meaning
Message
Event off
OFF
PV upper limit
PV-H
PV lower limit
PV-L
Time event
TIME
Range of auxiliary
setting 1
Message
Unused
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Unused
Range of auxiliary
setting 2
Message
Unused
Unused
Unused
Unused
Setting category
Operation category
—
—
Segment type
PV type
Segment type
PV type
Segment type
Time type
Event type
4
6
7
5
Meaning
Message
Upper deviation limit
DEV-H
Deviation rate upper limit
wait DEV-H-W
Deviation lower limit with
stanby DEV-L-W
Lower deviation limitt
DEV-L
Range of auxiliary
setting 1
Message
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Range of auxiliary
setting 2
Message
Unused
Unused
Unused
Unused
Setting category
Operation category
Segment type
PV type
Segment type
PV type
Segment type
PV type
Segment type
PV type
Event type
8
10
11
9
Meaning
Message
Absolute value deviation
upper limit A-DEV-H
Absolute value deviation rate upper
limit with stanby A-DEV-H-W
Absolute value deviation lower limit
with stanby A-DEV-L-W
Absolute value deviation
lower limit A-DEV-L
Range of auxiliary
setting 1
Message
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Range of auxiliary
setting 2
Message
Unused
Unused
Unused
Unused
Setting category
Operation category
Segment type
PV type
Segment type
PV type
Segment type
PV type
Segment type
PV type
Event type
12
14
15
13
Meaning
Message
PV deviation rate upper
limit A-DEV-H
SP upper limit
SP-H
SP lower limit
SP-L
PV deviation rate lower
limit D-PV-L
Range of auxiliary
setting 1
Message
Sampling cycle 0.1 to
600.0sec
sampling rate
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Sampling cycle 0.1 to
600.0sec
sampling rate
Range of auxiliary
setting 2
Message
Unused
Unused
Unused
Unused
Setting category
Operation category
Segment type
PV type
Segment type
PV type
Segment type
PV type
Segment type
PV type
Chapter 7. PARAMETER SETUP