12-3
Item
Specifications
Mode
Control section
Program run mode
READY
RUN
HOLD
FAST
END
READY FAST
Proportional band (P)
Output section
PID control
0.0 to 1000.0% (0.0: On-off control)
Integral time (I)
0 to 3600s (0: PD control)
Derivative time (D)
0 to 1200s (0: PI control)
Manipulated variable
limit
Low-limit
: -5.0% to high-limit
High-limit : Low-limit to +105.0%
Manual reset
0.0 to 100.0%
Programmer function
Auxiliary output
Auto tuning
Automatic setting of PID value by limit cycle method
Manipulated variable change 0.1 to 110.0%/0.1s
On-off control differential
0 to 1000U
Scaling
Possible
Scaling
Possible
Selection
Manipulated variable output is selectable to SP output
Type
PV, SP, deviation, MV, PV1, PV2
Output resolution
1/10000
PID groups selection
Segment specified, automatic zone selectable during
program run
No. of PID groups
16 groups for program operation (9 segment specific
and 7 automatic zone selecting)
Fixed command control
mode
READY
: Preparation state (control stop)
RUN : Run state
AUTO : Automatic run state
MANUAL : Manual run state (output is operatable to console)
AUTO
: Automatic run state
MANUAL
: Manual run state (Enables manual output from system console.)
Normal reverse operation selection
Selection is settable
Current output (5G)
Auxiliary output CH1, CH2
: Preparation state (control stop, select of program number is possible.)
: Advancing run state
: Hold run state
: Fast feed run state
: End point run state
: Preparation and the fast feed state
: 4 to 20mAdc
: Lower than 600
Ω
(under operating conditions)
: Lower than 0.1% FS (under the standard conditions)
: 1/10000
: 21.6mAdc
: 2.4mAdc
: 0.1s
: Lower than 25V
Output current
Allowable load resistance
Output accuracy
Output resolution
Max. output current
Min. output current
Output update cycle
Open time terminal voltage
Chapter 12. SPECIFICATIONS