7-6
PA 31
Event on delay
Group 1 event number
31
0 to 16
[Description:]
A setting of 0 generates no delay.
0
PA 32
Event on delay
Group 1 delay time
32
0.0 to 3000.0sec
[Description:]
When
PA31
is set to 0, “-----” is displayed and setting is not possible.
0.0
PA 33
Event on delay
Group 2 event number
33
0 to 16
[Description:]
A setting of 0 generates no delay.
0
PA 34
Event on delay
Group 2 delay time
34
0.0 to 3000.0sec
[Description:]
When
PA33
is set to 0, “-----” is displayed and setting is not possible.
0.0
PA 35
Event on delay
Group 3 event number
35
0 to 16
[Description:]
A setting of 0 generates no delay.
0
PA 36
Event on delay
Group 3 delay time
36
0.0 to 3000.0sec
[Description:]
When
PA35
is set to 0, “------” is displayed and setting is not possible.
0.0
PA 37
Event on delay
Group 4 event number
37
0 to 16
[Description:]
A setting of 0 generates no delay.
0
PA 38
Event on delay
Group 4 delay time
38
0.0 to 3000.0sec
[Description:]
When
PA37
is set to 0, “-----” is displayed and setting is not possible.
0.0
PA 41
EG1 LED display event
number
41
0 to 16
[Description:]
A setting of 0 turns off the EG1 LED.
0
PA 42
EG2 LED display event
number
42
0 to 16
[Description:]
A setting of 0 turns off the EG2 LED.
0
PA 43
PID computation initialize
43
0: No initialization during advance processing and PID
group change.
1: Initializes during advance processing but not during
PID group change.
2: No initialization during advance processing but
initializes during PID group change
3: Initializes both during advance processing and PID
group change
0
PA 39
FAST X
39
0 : 2X
1 : 10X
2 : 60X
3 : 120X
[Description:]
When setup data
C62
is set to 1 (program time unit: minutes,
seconds), settings 3 and 4 produce a speed of 10 X.
When
C62
is set to 2 (program time unit: 0.1sec), the FAST
mode is not available.
0
[Description:]
“-----”is displayed and setting is not possible.
-----
PA 24
24
Unused
-----
PA 25
25
Unused
-----
PA 26
26
Unused
-----
PA 27
27
Unused
-----
PA 28
28
Unused
-----
PA 29
29
Unused
-----
PA 30
30
Unused
[Description:]
“-----”is displayed and setting is not possible.
----
PA 44
44
Unused
[Description:]
“-----”is displayed and setting is not possible.
-----
PA 40
40
Unused
----
PA 45
45
Unused
0.1 to 60.0sec
2.0
PA 46
46
G.SOAK time
----
PA 47
47
Unused
----
PA 48
48
Unused
----
PA 49
49
Unused
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
Chapter 7. PARAMETER SETUP