7-26
0
C
72
72
External switch input RSW6
0
C
73
73
External switch input RSW7
0
C
74
74
External switch input RSW8
0: BCD4 bit x 2 digits
1: binary 7 bits
0
C
75
75
External switch input RSW9
to 16 (program selection)
0 to 127
[Description:]
“-----” is displayed and setting is not possible on model
without communications.
When
C76
is set to 0, the communication function is not
activated.
0
C
76
76
Communication address
0: 9600bps
1: 4800bps
2: 2400bps
3: 1200bps
[Description:]
“-----” is displayed and setting is not possible on model
without communications.
0
C
77
77
Transmission rate
0: 8 bits, even parity, 1 stop bit
1: 8 bits, no parity, 2 stop bits
[Description:]
“-----” is displayed and setting is not possible on model
without communications.
0
C
78
78
Transmission code
0: CPL
1: ST221 (no PV trend)
2: ST221 (PV trend)
[Description:]
“-----” is displayed and setting is not possible on model
without communications.
0
C
79
79
Communication
0 : RS-485
1 : RS-232C
[Description:]
“-----” is displayed and setting is not possible on model
without communications.
0
C
80
80
Communication method
[Description:]
Can only be referenced for mechanical service use.
–
C
81
81
ROM ID
–
C
82
82
ROM ITEM
–
C
83
83
ROM revision
–
C
85
85
CPU board ID
–
C
86
86
I/O board ID
[Description:]
“-----” is displayed and setting is not possible.
----
C
87
87
Unused
----
C
88
88
Unused
----
C
89
89
Unused
1
C
90
90
PID type
0: Yes
1: No
0
C
91
91
PV1 burnout
0: Yes
1: No
[Description:]
“-----” is displayed and setting is not possible on model
with one PV input channel.
0
C
92
92
PV2 burn out
0: Does not go on a second time off in time proportional cycle.
1: Goes on a second time in time proportional cycle.
0
C
93
93
Time proportional output system
–
C
84
84
Data version
0
C 71
71
External switch input RSW5
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
0: Improved
1: Compatible with Mark
I
0 : NOP (does not function)
1 : RAMP-E
2 : FAST
3 : G.SOAK is cleared using OR
4 : G.SOAK is cleared using AND
5 : AUTO/MANUAL
6 : AT
7 : PV1/PV2
8 : Auto load
9 : PV1 PV2 wait
10: PV2 PV1 wait
11: NOP (does not function)
12: Normal operation/reverse operation
Chapter 7. PARAMETER SETUP